UPS ELECTRICAL INSTALLATION
5.Wire the UPS for the proper input voltage as shown in Figure 28.
Universal power modules (model
C A U T I O N
Confirm that the UPS is wired for the proper input voltage as shown in Figure 28, and that the proper power modules (either
(a) | (b) Universal Power Modules |
100/200, 110/220, 120/208, 120/240, 127/220 Vac | 200, 208, 220, 230, and 240 Vac |
L2
L1
N
3 2 1
L1
L2/N
3 2 1
GND
GND
Figure 28. UPS Input Wiring
6.For units manufactured before 2009 that have an isolated transformer option. See Chapter 5, “Isolated Output Wiring Diagrams” on page 53 to complete the wiring for isolated output.
7.See the wiring diagrams beginning on page 48 for output configurations. Make UPS output connections on the backplane board terminating studs. Compression lugs (supplied in the accessory kit) may be installed on the proper terminating studs. Wires may also be terminated with ring terminals, which are attached to the output terminating studs.
Eaton 9170+ UPS | 45 |