UPS WITH BYPASS ELECTRICAL INSTALLATION

Figure 18 and Figure 19 describe output wiring configurations for various output voltages. You must also set the operating

menu 4 2 4 for the required output voltage as shown in the wiring configuration drawings.

NOTE For Eaton 9170+ UPS models with low-voltage hardwire output, it is recommended to divide the total load as equally as possible between X1 and X2, as shown in Figure 18.

NOTE Failure to balance the loads may cause an overload alarm even if the full capacity of the UPS has not been reached.

X1

X2

50 or 60 Hz

100/200, 110/220, 127/220, 120/208, or 120/240V Out Menu 4 2 4 set to 200, 220, 208, or 240, as required.

X2

 

 

X1

 

 

 

N/-DC

 

 

 

 

 

 

 

 

 

 

 

 

 

X

 

 

X

 

 

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200, 220

 

 

 

100, 110, 127, or 120

 

 

 

 

 

208, or 240

 

 

50%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100, 110, 127, or 120

 

 

 

L2

 

 

L1

50%

 

 

N

Figure 18. Split-Phase Power Modules

NOTE The factory-default wiring for all high-voltage receptacles in a chassis without a power cord is 3-wire plus ground input. If you have a universal power module (ASY-0674), all receptacles MUST be re-wired for a 2-wire plus ground input configuration as shown in Figure 19.

50 or 60 Hz

200, 208, 220, 230, or 240V Out *

Menu 4 2 4 set to 200, 208, 220, 230, or 240, as required.

X2

X1

 

X

N/-DC

X

*

L1L2/N

Figure 19. Universal Power Modules

12.Unscrew and remove the top rear cover of the cabinet and locate the terminal block.

Eaton 9170+ UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality

31

Page 37
Image 37