UPS STARTUP
2.Select the desired language for the display. Use the Y and B buttons to scroll between English, French, German, and Spanish. Enter your selection by pressing the button.
3.Set the clock for the local time and date. If the time or the date is correct as displayed, press the button to advance to the next configuration setting. Time must be entered in
Press the <- and button.
Set Time
time 14:51:38
<− −> ESC
4.The output voltage is the most important operating parameter you must set as part of the initial configuration screens. Select the desired UPS output voltage using the Y and B buttons. Possible selections are 200, 208, 220, 230, and 240 Vac. (Low voltages are derived from these voltages, as listed in Table 5 on page 34 and Table 9 on page 53.) Press the button when the desired output value is displayed.
5.If the system includes any external battery cabinets, record the
External Capacity extamphr 0028.8
<− −> ESC