UPS STARTUP
Eaton 9170+ UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 75
2. Select the desired language for the display. Use the
Y
and
B
buttons to scroll between English, French, German, and Spanish.
Enter your selection by pressing the button.
3. Set the clock for the local time and date. If the time or the date is
correct as displayed, press the button to advance to the next
configuration setting. Time must be entered in 24-hour format.
Press the <- and -> buttons to move left and right. Press the
Y
and
B
buttons to increase or decrease the value of each selected digit.
When the displayed value is correct, press the button.
Set Timetime 14:51:38 < > ESC
4. The output voltage is the most important operating parameter you
must set as part of the initial configuration screens. Select the
desired UPS output voltage using the
Y
and
B
buttons. Possible
selections are 200, 208, 220, 230, and 240 Vac. (Low voltages are
derived from these voltages, as listed in Table 5 on page 34 and
Table 9 on page 53.) Press the button when the desired output
value is displayed.
5. If the system includes any external battery cabinets, record the
ampere-hour capacity of batteries installed in these cabinets. If
using a standard cabinet, count the number of battery strings (two
battery modules side-by-side equals one string). Each battery string
contains 7.2 ampere-hours. Enter the total value in the next startup
screen.
External Capacityextamphr 0028.8 < > ESC