SPECIFICATIONS

Table 16. Model Specifications for Split-Phase Power Modules (ASY-0673) (continued)

Nine- and Twelve-Slot Cabinet

CAUTION Do NOT install more than seven power and/or battery charger modules in a 9- or 12-slot cabinet.

Optional

UPS

Input Current

Output Current

Recommended

Heat

Chargers

kVA/Watts

(200V)

(100/200V, 110/220V, 120/240V)

Input Service

Dissipation

 

 

 

 

 

 

0

12/10000

64A

60A, 56A, 50A

80A

1145W

 

 

 

 

 

(3.90 kBTU/hr)

 

 

 

 

 

 

1

12/10000

80A

60A, 56A, 50A

100A

1430W

 

 

 

 

 

(4.88 kBTU/hr)

 

 

 

 

 

 

2

12/10000

96A

60A, 56A, 50A

125A

1720W

 

 

 

 

 

(5.85 kBTU/hr)

 

 

 

 

 

 

3

12/10000

102A**

60A, 56A, 50A

125A

1995W

 

 

 

 

 

(6.75 kBTU/hr)

 

 

 

 

 

 

0

15/12500

80A

75A, 70A, 62.5A

100A

1430W

 

 

 

 

 

(4.88 kBTU/hr)

 

 

 

 

 

 

1

15/12500

96A

75A, 70A, 62.5A

125A

1720W

 

 

 

 

 

(5.85 kBTU/hr)

 

 

 

 

 

 

2

15/12500

102A**

75A, 70A, 62.5A

125A

1995W

 

 

 

 

 

(6.75 kBTU/hr)

 

 

 

 

 

 

0

18/15000

96A

90A, 84A, 75A

125A

1720W

 

 

 

 

 

(5.85 kBTU/hr)

 

 

 

 

 

 

1

18/15000

102A**

90A, 84A, 75A

125A

1995W

 

 

 

 

 

(6.75 kBTU/hr)

 

 

 

 

 

 

*In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in the system. For redundant power module operation (N+X), increase the input current rating by 2A for each additional redundant power module.

** Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external battery cabinet XXXXX-Model/Batt4.

100

Eaton 9170+ UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality

Page 106
Image 106
Eaton Electrical ASY0567, ASY0673, ASY0529, ASY0674 manual 100