SPECIFICATIONS

Table 17. Model Specifications for Universal Power Modules (XXXXX-Model/03 and ASY-0674)

Three-Slot Cabinet

Optional

UPS

Input Current for

Output Current for

Recommended

Heat

Chargers

kVA/Watts

200/208/220/230/240V*

200/208/220/230/240V

Input Service*

Dissipation

 

 

 

 

 

 

NA

3/2100

14/13.5/13/12.5/12A

15/14.5/14/13/12.5A

25A

285W

 

 

 

 

 

(0.98 kBTU/hr)

 

 

 

 

 

 

Six-Slot Cabinet

CAUTION Do NOT install more than three power and/or battery charger modules in a 6-slot cabinet.

Optional

UPS

Input Current for

Output Current for

Recommended

Heat

Chargers

kVA/Watts

200/208/220/230/240V

200/208/220/230/240V

Input Service

Dissipation

 

 

 

 

 

 

0

3/2100

14/13.5/13/12.5/12A

15/14.5/14/13/12.5A

25A

285W

 

 

 

 

 

(0.98 kBTU/hr)

 

 

 

 

 

 

1

3/2100

30/29.5/29/28.5/28A

15/14.5/14/13/12.5A

40A

570W

 

 

 

 

 

(1.95 kBTU/hr)

 

 

 

 

 

 

2

3/2100

46/45.5/45/44.5/44A

15/14.5/14/13/12.5A

60A

860W

 

 

 

 

 

(2.93 kBTU/hr)

 

 

 

 

 

 

0

6/4200

28/27/26/25/24A

30/29/28/26/25A

40A

570W

 

 

 

 

 

(1.95 kBTU/hr)

 

 

 

 

 

 

1

6/4200

44/43/42/41/40A

30/29/28/26/25A

60A

860W

 

 

 

 

 

(2.93 kBTU/hr)

 

 

 

 

 

 

0

9/6300

42/40.5/39/37.5/36A

45/43.5/42/39/37.5A

60A

860W

 

 

 

 

 

(2.93 kBTU/hr)

 

 

 

 

 

 

Nine- and Twelve-Slot Cabinet

CAUTION Do NOT install more than seven power and/or battery charger modules in a 9- or 12-slot cabinet.

Optional

UPS

Input Current for

Output Current for

Recommended

Heat

Chargers

kVA/Watts

200/208/220/230/240V

200/208/220/230/240V

Input Service

Dissipation

 

 

 

 

 

 

0

3/2100

14/13.5/13/12.5/12A

15/14.5/14/13/12.5A

25A

285W

 

 

 

 

 

(0.98 kBTU/hr)

 

 

 

 

 

 

1

3/2100

30/29.5/29/28.5/28A

15/14.5/14/13/12.5A

40A

570W

 

 

 

 

 

(1.95 kBTU/hr)

 

 

 

 

 

 

*In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in the system. For redundant power module operation (N+X), increase the input current rating by 2A for each additional redundant power module.

** Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external battery cabinet XXXXX-Model/Batt4.

Eaton 9170+ UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality

101

Page 107
Image 107
Eaton Electrical ASY0674, ASY0673, ASY0529, ASY0567 manual Three-Slot Cabinet Optional, Input Current for Output Current for