UPS ELECTRICAL INSTALLATION
The following notes are referenced in the system wiring diagrams (Figure 32 through Figure 34).
NOTE 1 The customer must provide input overcurrent protection. See NEC Section
NOTE 2 The customer must size the AC circuit conductors. All AC circuit conductors, including the neutral conductor, must be the same size (ampacity), have the same rating (75°C) copper wire, and be sized according to the input circuit breaker. See Table 7 on page 41 for recommended wire sizes. The UPS input and output conductors must be run through separate conduits.
NOTE 3 The customer must provide output overcurrent protection. See NEC Section
NOTE 4 See “Equipment Clearances” on page 9 for installation and service clearances before installing the UPS. Use flexible conduit on the UPS or the external battery cabinet if either must be moved.
NOTE 5 External UPS battery cabinets are optional. See “Battery Cabinet Installation” on page 61 for installation instructions.
NOTE 6 UPS output circuits shall be installed in dedicated conduit systems and not shared with other electrical circuits.
Eaton 9170+ UPS | 49 |