UPS STARTUP

6.The system signals an alarm when the required output cannot be maintained with the loss of redundant power modules. The alarm is essentially disabled with a redundancy level set at 0.

If you want the system to notify you when the number of redundant power modules is less than a specified level, enter a redundancy level. Each increment above 0 indicates the number of modules that can be removed from operation before the alarm occurs. This setting affects only the alarm; the system continues to operate as an N+X system even if this parameter is left at the default value of 0.

Set Redundancy

RSetting 0

<− −> ESC

7.To password-protect the UPS On/Off function, press the Y or B button to make your selection; then press the button. If a password is required, the UPS On and Off functions are accessible only after first entering the correct password value (0377).

ON OFF Password?

No

ESC

8.The UPS is now ready to operate, and displays the normal On/Off function screen.

Press the ON button on this screen to start the UPS.

These configuration parameters are accessible during normal UPS operation by pressing the Config button through the front panel display.

76

Eaton 9170+ UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality

Page 82
Image 82
Eaton Electrical ASY0567, ASY0673, ASY0529, ASY0674 manual Esc