UPS WITH BYPASS ELECTRICAL INSTALLATION

7.Find the terminal strip inside the bypass switch cabinet. Using the label on the back of the bypass switch access cover and the proper installation wiring diagram, make the terminal strip connections and tighten all connections as specified in Table 2 on page 22. Use copper wire that is the appropriate size for the current draw.

Figure 16 shows a sample label.

Figure 16. Bypass Switch Wiring Label

8.After installing bypass switch wiring, torque the screws holding all input and output power conductors to the values specified in Table 2 on page 22.

Eaton 9170+ UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality