OPERATION

Table 12 lists the alarm log messages.

Table 12. Alarm Log Messages

Message

Explanation

 

 

Open Cell

Battery failure caused by open cell.

 

 

Weak Battery

Battery failure caused by load test.

 

 

Phase Error

Internal error – contact your service representative.

 

 

Module Failure

Internal error – contact your service representative.

 

 

Excessive Transfers

Internal error – contact your service representative.

 

 

Precharge Failure

Internal error – contact your service representative.

 

 

Insufficient Batteries

Too few battery modules; decrease load or add battery modules.

 

 

Insufficient Modules

Too few power modules; decrease load or add power modules.

 

 

Incompatible Module

A power module with incompatible firmware has been installed

 

in the system; contact your service representative.

 

 

Battery Test

NOTE The batteries must be fully charged and the UPS must not have been on battery within 24 hours of the battery test.

The Eaton 9170+ battery test runs automatically every 30 days by default and can also be performed manually. When the test is complete, the UPS automatically displays the results.

To initiate a manual test, select menu 3 1 1. Use menu 3 1 to set the battery test parameters, including the test interval and time of day.

During the battery test, the Eaton 9170+ performs an open cell test and displays the message “Open Cell Test” (firmware versions 2.22 and later) or “Open Cell” (firmware versions prior to 2.22). Both of these messages are different from the Open Cell alarm.