SPECIFICATIONS
Table 18. Environmental and Safety
Operating Temperature | 0°C to 40°C (32°F to 104°F) |
| Optimal battery performance: 25°C (77°F) |
Storage Temperature | UPS with battery modules: |
| UPS without batteries: |
Relative Humidity | |
|
|
Operating Altitude | Up to 3,050 meters above sea level (10,000 ft) |
| The maximum operating ambient temperature decreases 1°C per 300m above 1525m |
| (2°F per 1000 ft above 5000 ft) |
|
|
Up to 12,200m above sea level (40,000 ft) | |
|
|
Ventilation | The air around the UPS must be clean and free of dust, corrosive chemicals, and other |
| contaminants. The Eaton 9170+ UPS uses internal fans to circulate the air for cooling. |
| The air must be free to circulate around the UPS and battery cabinet(s). Do not operate |
| the UPS in a sealed room or container. |
|
|
Audible Noise | Less than 53 dBA |
|
|
Surge Suppression | ANSI C62.41 Category B (formerly IEEE 587); IEC |
|
|
Safety Conformance | CAN/CSA C22.2, No. 107.1; UL 1778; |
| EN |
Agency Markings | UL, cUL, TÜV, CE, |
|
|
EMC (Class A) | EN |
|
|
Table 19. Battery
Configuration | (2) 60V, 7.2 Ah batteries per string |
|
|
Voltage | 120 Vdc |
|
|
Type | Sealed, maintenance‐free, valve‐regulated, lead‐acid |
|
|
Charging | Recharge time: 4 hr after |
| discharge, using standard internal battery charger. |
| Optional battery chargers at higher current ratings will be available for future product |
| release. |
|
|
104 | Eaton 9170+ UPS |