TROUBLESHOOTING
Question: “How do I... ” | Answer | ||||||
|
|
|
|
|
|
|
|
Check the condition of the | The results of the most recent battery test are stored at menu 3 1 2 1. To run a test of | ||||||
batteries? | battery condition, go to menu 3 1 1 and press the |
| button. When the test is complete, | ||||
| |||||||
| the results are again stored in the Battery Results parameter. | ||||||
|
|
|
|
|
| ||
Change the battery | This parameter requires a trained person, knowing the correct password, to perform. | ||||||
Without the proper password, you are able to only view operating limits, not change | |||||||
threshold? (or any other | them. Only authorized personnel should change these limits. For information about | ||||||
alarm or operating limit?) | making this or other | ||||||
| representative. | ||||||
|
|
|
|
|
| ||
Apply power to the load if | Turn the optional external bypass switch to either the SERVICE or the LINE position. In | ||||||
the unit will not operate? | these two positions, utility power flows directly to the load. In the SERVICE position, the | ||||||
| UPS does not receive utility power and may be worked on for maintenance purposes. | ||||||
|
|
|
|
|
| ||
Turn the external bypass | If the bypass switch is a | ||||||
switch? | beside the switch before turning the switch. | ||||||
|
|
|
| ||||
Set the UPS to turn on in | Go to menu 4 1. Select the system mode desired at | ||||||
High Efficiency mode? | Y or B button. When the display shows Auto High Efficiency, press the |
| button. | ||||
| |||||||
| |||||||
Set the UPS to operate in | The Eaton 9170+ system will not change operating modes as a timed event. But, if you | ||||||
High Efficiency mode on | wish to conserve energy, before leaving for the weekend, go to menu 4 1. Select High | ||||||
weekends? | Efficiency and press the button. After the weekend, return to the Automatic mode by | ||||||
going to menu 4 1 again, and selecting Auto followed by pressing the button. |
|
| |||||
|
|
| |||||
|
| ||||||
|
| ||||||
Change the level of system | To view or change the redundancy level, go to menu 4 2 5. | ||||||
redundancy? |
|
|
|
|
|
|
|
|
| ||||||
Change the batteries? | Each | ||||||
| See “Battery Replacement” on page 94 for the battery replacement procedure. | ||||||
|
| ||||||
Add/delete one or more | Physically install or remove battery modules as described on page 67. Record capacity | ||||||
strings of batteries? | of external battery strings (in all external battery cabinets) by going to menu 4 2 6. | ||||||
|
| ||||||
Add/delete one or more | Physically install or remove power modules as described on page 67. The system | ||||||
power modules? | operating software senses the number and location of all power modules in the | ||||||
| cabinet. If you want to change the number of redundant power modules, go to | ||||||
| menu 4 2 5 and change the level of system redundancy. | ||||||
|
|
|
|
|
|
|
|
108 | Eaton 9170+ UPS |