SPECIFICATIONS
Table 17. Model Specifications for Universal Power Modules
Nine- and Twelve-Slot Cabinet
CAUTION Do NOT install more than seven power and/or battery charger modules in a 9- or
Optional | UPS | Input Current for | Output Current for | Recommended | Heat |
Chargers | kVA/Watts | 200/208/220/230/240V | 200/208/220/230/240V | Input Service | Dissipation |
|
|
|
|
|
|
4 | 9/6300 | 102A** | 45/43.5/42/39/37.5A | 125A | 1995W |
|
|
|
|
| (6.75 kBTU/hr) |
|
|
|
|
|
|
0 | 12/8400 | 56/54/52/50/48A | 60/58/56/52/50A | 80A | 1145W |
|
|
|
|
| (3.90 kBTU/hr) |
|
|
|
|
|
|
1 | 12/8400 | 72/70/68/66/64A | 60/58/56/52/50A | 100A | 1430W |
|
|
|
|
| (4.88 kBTU/hr) |
|
|
|
|
|
|
2 | 12/8400 | 88/86/84/82/80A | 60/58/56/52/50A | 125A | 1720W |
|
|
|
|
| (5.85 kBTU/hr) |
|
|
|
|
|
|
3 | 12/8400 | 102/102/100/98/96A** | 60/58/56/52/50A | 125A | 1995W |
|
|
|
|
| (6.75 kBTU/hr) |
|
|
|
|
|
|
0 | 15/10500 | 70/67.5/65/62.5/60A | 75/72.5/70/65/62.5A | 100A | 1430W |
|
|
|
|
| (4.88 kBTU/hr) |
|
|
|
|
|
|
1 | 15/10500 | 86/83.5/81/78.5/76A | 75/72.5/70/65/62.5A | 125A | 1720W |
|
|
|
|
| (5.85 kBTU/hr) |
|
|
|
|
|
|
2 | 15/10500 | 102/99.5/97/94.5/92A** | 75/72.5/70/65/62.5A | 125A | 1995W |
|
|
|
|
| (6.75 kBTU/hr) |
|
|
|
|
|
|
0 | 18/12600 | 84/81/78/75/72A | 90/87/84/78/75A | 125A | 1720W |
|
|
|
|
| (5.85 kBTU/hr) |
|
|
|
|
|
|
1 | 18/12600 | 100/97/94/91/88A** | 90/87/84/78/75A | 125A | 1995W |
|
|
|
|
| (6.75 kBTU/hr) |
|
|
|
|
|
|
*In
** Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external battery cabinet
Eaton 9170+ UPS | 103 |