SPECIFICATIONS
Table 16. Model Specifications for Split-Phase Power Modules (ASY-0673) (continued)
Nine- and Twelve-Slot Cabinet
CAUTION Do NOT install more than seven power and/or battery charger modules in a 9- or
Optional | UPS | Input Current | Output Current | Recommended | Heat |
Chargers | kVA/Watts | (200V) | (100/200V, 110/220V, 120/240V) | Input Service | Dissipation |
|
|
|
|
|
|
3 | 3/2500 | 64A | 15A, 14A, 12.5A | 80A | 1145W |
|
|
|
|
| (3.90 kBTU/hr) |
|
|
|
|
|
|
4 | 3/2500 | 80A | 15A, 14A, 12.5A | 100A | 1430W |
|
|
|
|
| (4.88 kBTU/hr) |
|
|
|
|
|
|
5 | 3/2500 | 96A | 15A, 14A, 12.5A | 125A | 1720W |
|
|
|
|
| (5.85 kBTU/hr) |
|
|
|
|
|
|
0 | 6/5000 | 32A | 30A, 28A, 25A | 40A | 570W |
|
|
|
|
| (1.95 kBTU/hr) |
|
|
|
|
|
|
1 | 6/5000 | 48A | 30A, 28A, 25A | 60A | 860W |
|
|
|
|
| (2.93 kBTU/hr) |
|
|
|
|
|
|
2 | 6/5000 | 64A | 30A, 28A, 25A | 80A | 1145W |
|
|
|
|
| (3.90 kBTU/hr) |
|
|
|
|
|
|
3 | 6/5000 | 80A | 30A, 28A, 25A | 100A | 1430W |
|
|
|
|
| (4.88 kBTU/hr) |
|
|
|
|
|
|
4 | 6/5000 | 96A | 30A, 28A, 25A | 125A | 1720W |
|
|
|
|
| (5.85 kBTU/hr) |
|
|
|
|
|
|
5 | 6/5000 | 102A** | 30A, 28A, 25A | 125A | 1995W |
|
|
|
|
| (6.75 kBTU/hr) |
|
|
|
|
|
|
0 | 9/7500 | 48A | 45A, 42A, 37.5A | 60A | 860W |
|
|
|
|
| (2.93 kBTU/hr) |
|
|
|
|
|
|
1 | 9/7500 | 64A | 45A, 42A, 37.5A | 80A | 1145W |
|
|
|
|
| (3.90 kBTU/hr) |
|
|
|
|
|
|
2 | 9/7500 | 80A | 45A, 42A, 37.5A | 100A | 1430W |
|
|
|
|
| (4.88 kBTU/hr) |
|
|
|
|
|
|
3 | 9/7500 | 96A | 45A, 42A, 37.5A | 125A | 1720W |
|
|
|
|
| (5.85 kBTU/hr) |
|
|
|
|
|
|
4 | 9/7500 | 102A** | 45A, 42A, 37.5A | 125A | 1995W |
|
|
|
|
| (6.75 kBTU/hr) |
|
|
|
|
|
|
*In
** Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external battery cabinet
Eaton 9170+ UPS | 99 |