SPECIFICATIONS

Table 16. Model Specifications for Split-Phase Power Modules (ASY-0673) (continued)

Nine- and Twelve-Slot Cabinet

CAUTION Do NOT install more than seven power and/or battery charger modules in a 9- or 12-slot cabinet.

Optional

UPS

Input Current

Output Current

Recommended

Heat

Chargers

kVA/Watts

(200V)

(100/200V, 110/220V, 120/240V)

Input Service

Dissipation

 

 

 

 

 

 

3

3/2500

64A

15A, 14A, 12.5A

80A

1145W

 

 

 

 

 

(3.90 kBTU/hr)

 

 

 

 

 

 

4

3/2500

80A

15A, 14A, 12.5A

100A

1430W

 

 

 

 

 

(4.88 kBTU/hr)

 

 

 

 

 

 

5

3/2500

96A

15A, 14A, 12.5A

125A

1720W

 

 

 

 

 

(5.85 kBTU/hr)

 

 

 

 

 

 

0

6/5000

32A

30A, 28A, 25A

40A

570W

 

 

 

 

 

(1.95 kBTU/hr)

 

 

 

 

 

 

1

6/5000

48A

30A, 28A, 25A

60A

860W

 

 

 

 

 

(2.93 kBTU/hr)

 

 

 

 

 

 

2

6/5000

64A

30A, 28A, 25A

80A

1145W

 

 

 

 

 

(3.90 kBTU/hr)

 

 

 

 

 

 

3

6/5000

80A

30A, 28A, 25A

100A

1430W

 

 

 

 

 

(4.88 kBTU/hr)

 

 

 

 

 

 

4

6/5000

96A

30A, 28A, 25A

125A

1720W

 

 

 

 

 

(5.85 kBTU/hr)

 

 

 

 

 

 

5

6/5000

102A**

30A, 28A, 25A

125A

1995W

 

 

 

 

 

(6.75 kBTU/hr)

 

 

 

 

 

 

0

9/7500

48A

45A, 42A, 37.5A

60A

860W

 

 

 

 

 

(2.93 kBTU/hr)

 

 

 

 

 

 

1

9/7500

64A

45A, 42A, 37.5A

80A

1145W

 

 

 

 

 

(3.90 kBTU/hr)

 

 

 

 

 

 

2

9/7500

80A

45A, 42A, 37.5A

100A

1430W

 

 

 

 

 

(4.88 kBTU/hr)

 

 

 

 

 

 

3

9/7500

96A

45A, 42A, 37.5A

125A

1720W

 

 

 

 

 

(5.85 kBTU/hr)

 

 

 

 

 

 

4

9/7500

102A**

45A, 42A, 37.5A

125A

1995W

 

 

 

 

 

(6.75 kBTU/hr)

 

 

 

 

 

 

*In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in the system. For redundant power module operation (N+X), increase the input current rating by 2A for each additional redundant power module.

** Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external battery cabinet XXXXX-Model/Batt4.

Eaton 9170+ UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality

99

Page 105
Image 105
Eaton Electrical ASY0529, ASY0673, ASY0567, ASY0674 manual Model Specifications for Split-Phase Power Modules ASY-0673