HPMA User Guide

Attr.

Description

Recommended Action

Code

 

 

 

PTEn

Temperature State; an indication of the

There may be some issues with the

 

temperature status, summarizing the

cooling around the servers, and

 

RAID temperature situation:

measures should be implemented

 

0

= OK

to help keep the servers cool or to

 

1

= Temp Low

investigate if the temperature is

 

too low.

 

2 = Temp High

 

 

 

3

= Critical

 

 

4

= Unavailable

 

 

The letter n in the Attribute Code is an

 

 

indicator of which RAID, as some servers

 

 

are attached to multiple RAID units.

 

 

 

 

RMS1

RAID Monitor Status. This is an overall

If the monitor is “Disconnected”

 

indication of whether the RAID monitor

for an extended period, restart the

 

driver is connecting with the SSM service:

server. If this does not clear the

 

0

= Connected

problem, contact HP technical

 

1

= Connecting...

support.

 

 

 

2

= Disconnected

 

 

A status of “Disconnected” does not mean

 

 

that the RAID is faulty, only that the SSM

 

 

is unable to monitor it.

 

 

 

 

RSTU

FSG Replication status; whether the com-

If the device reports “No Pri-

 

ponent is:

mary”, ensure the primary FSG

 

0

= Normal

service of the replication group is

 

1

= No Primary

online and running normally. If

 

the status is “Error”, contact HP

 

2

= Error

 

technical support.

 

 

 

 

 

 

 

SAVP

Space Available; the percentage of storage

If the available space is reaching a

 

space remaining on all object stores of the

low threshold, you should start

 

server.

looking into either purchasing

 

Adjusting the alarm threshold allows you

additional storage or migrating

 

to proactively manage when additional

some data to archive, depending

 

storage needs to be purchased.

on your available options.

 

 

 

 

 

188

HP Medical Archive