Liebert UPS System user manual Repairing the failed UPS unit in parallel operation system

Models: UPS System

1 121
Download 121 pages 37.39 Kb
Page 103
Image 103

Chapter 8 Parallel System

2. Normal mode to bypass mode

Press the “inverter shutdown” button on the UPS panels one by one, all the UPS can transfer to bypass mode.

In the above operation, if the total capacity of all the inverters is smaller than the load capacity, all the UPS unit will transfer from normal mode to bypass mode.

3. Bypass mode to normal mode

Q1 has already been switched on, press the “inverter start” button on the UPS panels one by one until the total capacity of all inverters is bigger or equal to load capacity, all the UPS units will transfer from bypass mode to normal mode.

4. Battery mode to normal mode

If the utility is normal and the Q1 of all the UPS units are switched on, the UPS will transfer from battery mode to normal mode automatically.

5. Normal mode to maintenance bypass mode

Follow the Steps 14 in section 8.5.2 to switch the UPS from normal mode to maintenance bypass mode.

8.5.4 Repairing the failed UPS unit in parallel operation system

1. Shut down and isolate the failed UPS in parallel operation system

When some UPS unit fails in the system, isolate it and let other UPS units continue to operate, the procedures are given below:

1)press “inverter shutdown” button to shut down the inverter of the UPS. Note: Before switching off this UPS, verify whether the remaining UPS units can power the load;

2)switch off this failed UPS unit’s Q5, Q2 and Q1;

3)switch off this failed UPS unit’s battery switch QF1;

4)maintenance work can be done after waiting for 8 minutes( that is, after the DC bus capacitor discharges to zero voltage).

97

Page 103
Image 103
Liebert UPS System user manual Repairing the failed UPS unit in parallel operation system, Normal mode to bypass mode