Chapter 6 Maintenance
6.1.8 Input and output contacts
The functions of input and output contacts are introduced in Chapter 3.
1. Output dry contact
This UPS provides 8 kinds of dry contacts output and the definition is given below:
Battery low: This signal is active when the
Battery mode: This signal is active when the battery powers the load;
Inverter mode: This signal is active when the utility powers the inverter normally;
Ambient
Emergent shutdown: This signal is active when the UPS is shut down by user in emergency;
Common alarm: This signal is active when the UPS has fault;
Overload: This signal is active when the load is too heavy;
Generator mode: This signal is active when the generator powers the UPS;
2. Input contacts
The UPS can connect to 6
24V contacts for environment parameters (3 circuit branches):
12V contacts for environment parameters (1 circuit branch): ENV, suitable for connecting the 12V sensor for environment parameters, such as the water sensor. The contacts are relay dry contacts.
Generator contacts: These are the dry contacts of intelligent generator and are connected to the UPS input terminals. The contacts are used to notify the UPS that the generator has been connected. If the user wants to use intelligent generator mode, but the generator has no signal to transmit to these contacts, short connect the
Note:
If the user wants to use the generator mode, it is required that the UPS should be set to “Generator mode enabled” through the background host first. Otherwise, the generator signal is inactive.
75