Chapter 7 Troubleshooting
| No.1 |
| Fault description |
|
| Reason |
|
|
| Actions to be taken | ||||||
| 30 |
| Rectifier fan fails |
|
| Rectifier fan is abnormal |
| Replace the fan in time and the UPS can | ||||||||
|
|
|
|
|
|
|
|
| recover automatically |
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| ||||||||
| 31 |
| Rectifier contactor |
|
| Rectifier contactor can’t be closed or |
| Notify the service dept for repairing | ||||||||
|
|
| abnormal |
|
| opened normally |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| ||||||
| 32 |
| Auxiliary contactor |
|
| Auxiliary | contactor abnormal | can’t |
| Notify the service dept for repairing | ||||||
|
|
| abnormal |
|
| be closed or opened normally |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| |||||||||
| 33 |
| Auxiliary power supply |
| At least one auxiliary power supply |
| Notify the service dept for repairing | |||||||||
|
|
| 1 fails |
|
|
| fails |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
| The IGBT of rectifier has over |
|
|
|
|
|
| |||
| 34 |
| Rectifier over current |
| current resulting in the shut down of |
| Notify the service dept for repairing | |||||||||
|
|
|
|
|
|
| rectifier. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
| Inverter | is | asynchronous | with |
| Check if the bypass is normal. The fault | ||||
| 35 |
| Inverter asynchronous |
|
| alarm | stops automatically | after the | ||||||||
|
|
|
|
|
|
| bypass |
|
|
|
| bypass recovers normal |
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| ||||||||
| 36 |
| Inverter fails |
|
| Inverter output fails and shuts down |
| Notify the service dept for repairing | ||||||||
|
|
|
|
|
|
|
|
|
|
|
| |||||
| 137 |
| Inverter | heatsink | over |
| Inverter heatsink temperature is too |
| The UPS can | recover | automatically. | |||||
|
| temperature |
|
| high |
|
|
|
| Check the environment and ventilation | ||||||
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| 38 |
| Inverter fan fails |
| Inverter fan is abnormal |
|
| Replace the fan in time and the UPS can | ||||||||
|
|
|
|
| recover automatically |
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| ||||||||
| 39 |
| Inverter SCR fails |
|
| Inverter SCR fails and has no |
| Notify the service dept for repairing | ||||||||
|
|
|
|
|
|
| output. UPS shuts down |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |||||||||
| 40 |
| Auxiliary power supply |
| At least one auxiliary power supply |
| Notify the service dept for repairing | |||||||||
|
|
| 2 fails |
|
|
| fails |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
| The IGBT of inverter has over |
| Restart the inverter, if the fault can’t be | |||||||
| 41 |
| Inverter over current |
| current resulting in the shut down of |
| cleared, notify the service dept for | |||||||||
|
|
|
|
|
|
| inverter. |
|
|
|
| repairing. |
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
| Shutdown due to low |
| DC bus voltage is too low resulting |
| Check | whether | there is | fault | in rectifier | |||||
| 42 |
|
| in the shutdown of inverter |
|
| side, if no, then check whether overload | |||||||||
|
| bus voltage |
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
| occurs. Restart after clearing the fault. | ||||||
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
| |||||||||
| 43 |
| Output transformer |
| Output transformer temperature is |
| Auto recovery, ambient and ventilation of | |||||||||
|
| over temperature |
|
| too high |
|
|
|
| UPS should be checked. |
|
| ||||
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
| ||||||
| 44 |
| overload |
|
| Load is too heavy |
|
| Disconnect unnecessary load and ensure | |||||||
|
|
|
|
|
|
|
|
| the safety. |
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| ||||||||
| 45 |
| Overload exceeds |
|
| Over load occurs in inverter mode, |
| If the load decreases after 5 minutes, the | ||||||||
|
| normal time |
|
| transfers to bypass mode |
|
| system will back to inverter mode | ||||||||
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
| ||||||||
| 46 |
| Output fuse blows up |
| Output fuse blows |
|
| Notify the service dept for repairing | ||||||||
|
|
|
|
|
|
|
|
|
| |||||||
| 47 |
| AC | output | over |
| Output over voltage |
| Notify the service dept for repairing | |||||||
|
| voltage |
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| ||||||
| 48 |
| Output surge current |
| Surge current | occurs in bypass |
| Avoid applying big load abruptly and short | ||||||||
|
|
| mode, the system shutdown |
|
| circuit |
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|