Chapter 1 Introduction

Parameters of Liebert iTrust UPS are given in Table1-1

 

Capacity

 

 

20kVA

 

30kVA

 

40kVA

60kVA

 

 

 

 

 

 

 

 

 

 

Model

 

 

UL33-0200L

UL33-0300L

 

UL33-0400L

UL33-0600L

 

 

 

 

 

 

 

 

 

Input Voltage

 

 

380/400/415V(line-to-line voltage)

 

 

 

 

 

 

 

 

 

 

AC Power Input

 

 

Three-phase three-wire

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power Factor

 

 

>0.99

 

 

 

 

 

 

 

 

 

 

 

Harmonic Current

 

 

<4%(Voltage distortion lower than 2% at rated load)

 

 

 

 

 

 

 

 

 

 

 

Rectifier

Voltage Range

 

 

+15%~-20%

 

 

 

 

 

 

 

 

 

 

 

 

 

input

 

 

Lowest operating voltage: -45%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Current: <115%In for continuous operation; 115~140%In

 

Input current limiting

 

 

for 5 minutes;

140~165%In

for 1minute; Current limiting at

 

 

 

current over 165%In(In is the rated output current without

 

 

 

 

 

 

 

 

 

 

deration)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

frequency range

 

 

50Hz ±10%

 

 

 

 

 

 

 

 

 

 

 

Input Voltage

 

 

380/400/415V(line-to-line voltage)

 

 

 

 

 

 

 

 

 

 

 

Bypass input

Input Voltage Range

 

 

±10%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Power Input

 

 

Three-phase four-wire

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency range

 

 

50Hz±10%

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage regulation

 

 

380/400/415V±1%

 

 

 

 

(balanced load)

 

 

(±5% adjustable)

 

 

 

 

 

 

 

 

 

 

 

Voltage transient response

 

±5%(0~100%linear load)

 

 

 

 

 

 

 

 

 

 

 

 

Transient recovery time

 

<60ms

 

 

 

 

 

 

 

 

 

 

 

 

Voltage distortion(linear load)

 

THD<2%(line-to-neutral voltage)(battery float

charge state,

 

 

rated balance load)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage distortion(nonlinear

 

THD<5%(line-to-neutral voltage)(battery float charge state,

 

load)

 

 

 

rated balance load)

 

 

 

Output

 

 

 

 

 

 

 

 

 

 

Power Factor

 

 

0.8(lagged)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency Syn. Range

 

 

50Hz±2Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency regulation(Battery

±0.1%

 

 

 

 

 

 

mode)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Phase

Displacement

(Three-

120± 1°(balanced load or unbalanced load)

 

 

Phase)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage

unbalance

rate

at

±2%(battery float charge state)

 

 

100% unbalance load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency slew rate

 

 

<1Hz/s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

Page 15
Image 15
Liebert UPS System user manual Parameters of Liebert iTrust UPS are given in -1