Chapter 4 Commissioning of UPS

4.3.1 Check the function of the display panel

Press the button “inverter shutdown” for 2 seconds and check that the inverter stops.

Rectifier

 

 

Bypass

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery

Inverter

 

 

Load

 

 

Alarm

indicator

 

 

indicator

 

 

 

 

 

 

 

 

 

 

 

 

 

indicator

indicator

 

indicator

 

indicator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UL33-0400L 2001-11-08

12:50:30

 

Inv. On

Units

2/4

ID: 1

 

Out

Language

Chinese

 

Local

Chinese English

 

System

Com. Adress Set

1

 

± BatteryRecords

1

 

 

 

Date & Time Set

 

 

² Settings

 

 

2001£ 11- £ 08-

12:50:30

 

Input Breaker Closed 11£ 08-

12:09

 

Ê Byp. Breaker Closed 11£ 08-

12:09

 

Mains Volt. Abnormal

11£ 08-

12:28

m

Ê UPS in Battery Mode

11£ 08-

12:28

Ö Battery low

11£ 08-

12:50

 

 

 

11£ 08-

12:12

 

Emergency

shutdown

Alarm

F1

 

 

Inverter

Inverter

F2

 

 

 

stare

stop

 

 

 

 

 

 

F3

 

F4

 

Fault

Mute

clearing

 

Fig. 4-7 Display Panel

Press the button “Emergency shutdown” and check that the UPS shuts down Press the button “fault clear” to restart the UPS

Simulate a fault to check the visual and audible alarm functions.

Press “Mute” button to silence the alarm

4.3.2 Switching between operation mode

t

Fig. 4-8 UPS Circuit Breaker Operation

41

Page 47
Image 47