Chapter 4 Commissioning of UPS
4.3.1 Check the function of the display panel
Press the button “inverter shutdown” for 2 seconds and check that the inverter stops.
Rectifier |
|
| Bypass |
|
|
|
|
|
|
|
|
|
|
|
|
| Battery | Inverter |
|
| Load |
|
| Alarm | ||||||||||||||||||||||||||||||||||||||||||||||
indicator |
|
| indicator |
|
|
|
|
|
|
|
|
|
|
|
|
| indicator | indicator |
| indicator |
| indicator | ||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
12:50:30 |
| |||
Inv. On | Units | 2/4 | ID: 1 |
|
Out | Language | Chinese |
| |
Local | Chinese English |
| ||
System | Com. Adress Set | 1 |
| |
± BatteryRecords | 1 |
|
|
|
Date & Time Set |
|
| ||
² Settings |
|
| ||
2001£ 11- £ 08- | 12:50:30 |
| ||
Input Breaker Closed 11£ 08- | 12:09 |
| ||
Ê Byp. Breaker Closed 11£ 08- | 12:09 |
| ||
Mains Volt. Abnormal | 11£ 08- | 12:28 | m | |
Ê UPS in Battery Mode | 11£ 08- | 12:28 | ||
Ö Battery low | 11£ 08- | 12:50 |
| |
|
| 11£ 08- | 12:12 |
|
Emergency
shutdown
Alarm
F1
|
| Inverter | Inverter |
F2 |
| ||
|
| stare | stop |
|
| ||
|
| ||
|
|
F3 |
| |
F4 |
| |
Fault | Mute | |
clearing | ||
|
Fig. 4-7 Display Panel
Press the button “Emergency shutdown” and check that the UPS shuts down Press the button “fault clear” to restart the UPS
Simulate a fault to check the visual and audible alarm functions.
Press “Mute” button to silence the alarm
4.3.2 Switching between operation mode