Chapter 9 Optional Parts

h.Check whether the cables are well connected.

i.Use a 4mm2 cable to earth the lightning protection device.

j.Close the cover.

Note

1.All operations should be done with power off and confirm there is no dangerous voltage on the neutral line

2.Connect two pieces of PE cables from the lightning protection device. One cable is connected to the case of the UPS, the other one is connected to earthshorter than 30m, as short as possible.

3.After installation, switch on the circuit breaker of the lightning protection device, then the device is in normal operation state. If the circuit breaker is switched off, there will be no lightning protection functions. The circuit breaker is prohibited to be

switched off during normal operation of the lightning protection device

M

Equipment

User

Protection Earth

earthing bus bar

Fixing holes

lightning protection box

wiring diagram

circuit breaker

capper bar

Fig. 9-8 SPD24Z wiring