Chapter 10 Service after Sales

 

No.1

 

Fault description

 

 

 

 

Reason

 

 

 

Actions to be taken

 

 

34

 

Output surge current

 

Surge

current occurs

in bypass

 

Avoid applying

big

load abruptly

and

 

 

 

mode, the system shutdown

 

 

short circuit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transfer to bypass due to

 

The system transfers to bypass

 

Avoid applying

load

abruptly and

the

 

35

 

 

mode

due

to surge current

and

 

 

 

surge

 

 

 

back to inverter mode after load is

 

UPS can recover automatically

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

decreased

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In

parallel

operation

system,

 

 

 

 

 

 

 

 

 

 

 

 

some UPS module may require to

 

If the parallel operation system

 

 

 

Neighbouring UPS module

 

transfer to bypass due to surge or

 

transfers to bypass mode, and the

 

36

 

requires

to

transfer to

 

overload,

other

modules

will

 

operation condition

enables, all

the

 

 

 

bypass mode

 

 

transfer to bypass after receiving

 

UPS modules can recover to normal

 

 

 

 

 

the

signal

sent

by

this

UPS

 

 

 

 

 

 

 

 

module that requires to transfer to

 

mode synchronously.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

bypass mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

37

 

User’s wrong operation

 

Wrong operation such as start the

 

Operate with reference to User’s

 

 

 

UPS

with

the

maintenance

 

Manual

 

 

 

 

 

 

 

 

 

 

bypass switched on

 

 

 

 

 

 

 

 

 

 

The actual transfer times

 

Transfer times exceed the times

 

 

 

 

 

 

38

 

exceed

the

permissible

 

set by background. The system

 

Avoid frequent overload

 

 

 

transfer

times per hour

 

will stay in bypass mode until next

 

 

 

 

 

 

 

 

 

hour.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10.2 Warranty

We provide 1 year of free service for our UPS (including the battery).

The above warranty shall not apply in the following circumstances:

The battery is provided by user;

Damage resulting from operation not in accordance with the user manual;

Damage as a result of fire, flood, etc.;