Chapter 1 Introduction
| Capacity | 20kVA |
| 30kVA | 40kVA | 60kVA | |
|
|
|
|
|
| ||
| Model | ||||||
|
|
|
|
|
|
| |
| Insulation Resistance | >2M(500VDC) |
|
|
| ||
|
|
| |||||
| Dielectric Strength | (input to earth, output to earth)2820Vdc, leakage current lower | |||||
| than 3.5mA, 1min without arc |
|
| ||||
|
|
|
| ||||
|
|
| |||||
| Surge Immunity | Satisfy the class IV requirements specified by | |||||
System | ability to withstand 1.2/50us+8/20us not lower than 6kV/3kA | ||||||
| |||||||
|
|
|
|
|
| ||
| Protection index | IP20 |
|
|
| ||
|
|
|
|
| |||
Number of battery cells | 30 battery cells(12V) |
|
| ||||
|
|
|
| ||||
Installation | Cable access mode | top/bottom cable access modes optional |
| ||||
|
|
|
|
|
|
|
2. Electrical Parameters
For designing of utility power source,
Table
Model | |||||
|
|
|
|
| |
UPS rated power | 20kVA | 30kVA | 40kVA | 60kVA | |
|
|
|
|
| |
AC input | Rectifier: 380/400/415V+15%~(3¢3W), Bypass: 380/400/415V±10%(3¢4W) | ||||
|
|
|
|
| |
Rated loss | 2.40kW | 3.60kW | 4.37kW | 5.94kW | |
|
|
|
|
| |
Air intake(m3/hour) | 500 | 800 | 1400 | 2200 | |
|
|
|
|
| |
Rectifier input | 44A | 66A | 88A | 132A | |
current | |||||
|
|
|
| ||
|
|
|
|
| |
Bypass input current | 37A | 56A | 74A | 112A | |
|
|
|
|
| |
UPS output current | 37A | 56A | 74A | 112A | |
|
|
|
|
| |
Battery input current | 56A | 84A | 112A | 168A | |
|
|
|
|
|
11