Chapter 8 Parallel System

1.Press the “inverter shutdown” to shut down the inverter and the system transfers to bypass mode;

2.Switch off each UPS unit’s Q1 and the QF1 of battery cabinet;

3.Switch on each UPS unit’s Q3BP

4.Switch on each UPS unit’s Q2 and Q5

AT this time, the user’s load is totally dependent on the maintenance bypass of the UPS; Common checking or maintenance work can be done after waiting for 8 minutes( that is, after the DC bus capacitor discharges to zero voltage).

If the UPS requires to be switched off totally, switch on the KBPswitch off all the Q3BP switches, and then transfer the load to external maintenance bypass. Then the replacing or capacity expansion operation can be done after disconnecting the UPS input and output switches.

2. Shutdown in bypass mode

Follow the step 2-step 5 of “shutdown in normal mode” to shut down the UPS in bypass mode.

3. Shutdown in battery mode

If the utility is unavailable, conduct the step 1 of “shutdown in normal mode”, and then switch off all the switches.

4. Shutdown in united operation mode

The procedures of “shutdown in united operation mode” is the same with that of “shutdown in normal mode”.

8.5.3 Transferring between Operation Modes

When the parallel operation system is in normal mode, it can transfer between different operation modes, so the maintenance engineer can judge whether the system operate normally according to the transferring condition. If all the sources of the UPS is in normal range, conduct the following operations:

1. Normal mode to battery mode

Switch off all the UPS units’ Q1 and Q2the system will transfer from normal mode to battery mode.

96