Chapter 7 Troubleshooting
7.4 LCD indication for fault information
The LCD on the UPS displays the fault information of Table
|
|
|
|
|
|
|
|
|
| Table | Fault information |
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
| No.1 |
| Fault description |
|
|
| Reason |
|
|
|
|
|
| Actions to be taken |
|
| |||||
| 1 |
| Communication of |
| Communication between monitoring |
| Notify the service engineer for repairing | ||||||||||||||
|
|
| inverter fails |
|
| unit and inverter fails |
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| ||||||||||||||
| 2 |
| Communication of |
| Communication between monitoring |
| Notify the service engineer for repairing | ||||||||||||||
|
|
| rectifier fails |
|
| unit and rectifier fails |
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 3 |
| Ambient over- |
|
|
|
|
| Check the ventilation of UPS room |
|
| ||||||||||
|
| temperature |
|
|
|
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
| 4 |
| Environment |
|
| Environment | parameter | channel | 1 |
| Check the devices relating to the channel | ||||||||||
|
|
| parameter 1 abnormal |
| has alarm |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
| 5 |
| Environment |
|
| Environment | parameter | channel | 2 |
| Check the devices relating to the channel | ||||||||||
|
|
| parameter 2 abnormal |
| has alarm |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
| 6 |
| Environment |
|
| Environment | parameter | channel | 3 |
| Check the devices relating to the channel | ||||||||||
|
|
| parameter 3 abnormal |
| has alarm |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |||||||||||||
| 7 |
| Environment |
|
| 12V environment parameter channel |
| Check the devices relating to the channel | |||||||||||||
|
|
| parameter abnormal |
| has alarm |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
| 8 |
| Rectifier | input | voltage |
| voltage | of | rectifier |
| Check | the | voltage | ||||||||
|
| abnormal |
|
|
| exceeds normal operation range |
|
|
| amplitude of rectifier |
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
| Rectifier | input | under- |
|
| Check | the | voltage | |||||||||||
| 9 |
|
| lower than | 305V, but | higher | than |
| |||||||||||||
|
|
| voltage |
|
|
| 208V |
|
|
|
|
|
|
|
| amplitude of rectifier |
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| Rectifier’s input |
| Rectifier | frequency exceeds | the |
| Check | the | rectifier’s | input | voltage | ||||||||
| 10 |
| voltage frequency is |
|
| ||||||||||||||||
|
|
| normal range |
|
|
|
|
|
| frequency |
|
|
|
| |||||||
|
|
| abnormal |
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
| 11 |
| Input fuse blows |
| Rectifier input fuse blows up |
|
|
|
| Notify the service dept for repairing |
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |||||||||||
| 12 |
| Input transformer over |
| Temperature of input transformer is |
| Check | the | ambient temperature | and | |||||||||||
|
| temperature |
|
| too high |
|
|
|
|
|
|
|
| ventilation |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
| 13 |
| Input phase | rotation |
| Rectifier’s | input | phase | rotation | is |
| Notify | the UPS service | engineer, | check | ||||||
|
| reverse |
|
|
| reverse |
|
|
|
|
|
|
|
| the wiring of rectifier input cables |
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
| 14 |
| Input softstart fails |
| Input softstart fails |
|
|
|
|
| Notify the service dept for repairing |
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|