Chapter 3 Electrical Assemble

protective earth cable and lightning protection earth cable, should be 0.5 times of phase cable.

The relationship between the current and cross-sectional area is shown in Table 3- 2.

Table3-2 Recommended cross sectional area of cables

 

20kVA

30kVA

40kVA

60kVA

Name

 

 

 

 

 

 

 

 

Current

Cable

Current

Cable

Current

Cable

Current

Cable

 

(A)

(mm2)

(A)

(mm2)

(A)

(mm2)

(A)

(mm2)

 

 

 

 

 

 

 

 

 

Battery

56

25

84

25

112

35

168

50

 

 

 

 

 

 

 

 

 

Bypass

37

16

56

16

74

25

112

35

 

 

 

 

 

 

 

 

 

Output

37

16

56

16

74

25

112

35

 

 

 

 

 

 

 

 

 

Input

44

16

66

16

88

25

132

35

 

 

 

 

 

 

 

 

 

Neutral line

 

25

 

25

 

35

 

50

 

 

 

 

 

 

 

 

 

Earth cable

 

16

 

16

 

25

 

25

 

 

 

 

 

 

 

 

 

3.1.3 Selection of signal cables

Signal cables should use shielded multi-conductor cables. But if cable with single conductor is used, the different cables should be bonded together to increase the mechanical strength. The number of the bonded cables should not exceed 30. The cross-sectional area of the cable with single conductor should be at least 0.5 sq-

mm.Serial communication cables should use 3 or 5 shielded conductor cables.

3.2Cable connections

3.2.1Power cables

1.Cabling layout

Cabling layout is shown in Figures 3-1 and 3-2. For single input UPS, the rectifier input and bypass input are connected together.