Chapter 3 Electrical Assemble
protective earth cable and lightning protection earth cable, should be 0.5 times of phase cable.
The relationship between the current and
| 20kVA | 30kVA | 40kVA | 60kVA | ||||
Name |
|
|
|
|
|
|
|
|
Current | Cable | Current | Cable | Current | Cable | Current | Cable | |
| (A) | (mm2) | (A) | (mm2) | (A) | (mm2) | (A) | (mm2) |
|
|
|
|
|
|
|
|
|
Battery | 56 | 25 | 84 | 25 | 112 | 35 | 168 | 50 |
|
|
|
|
|
|
|
|
|
Bypass | 37 | 16 | 56 | 16 | 74 | 25 | 112 | 35 |
|
|
|
|
|
|
|
|
|
Output | 37 | 16 | 56 | 16 | 74 | 25 | 112 | 35 |
|
|
|
|
|
|
|
|
|
Input | 44 | 16 | 66 | 16 | 88 | 25 | 132 | 35 |
|
|
|
|
|
|
|
|
|
Neutral line |
| 25 |
| 25 |
| 35 |
| 50 |
|
|
|
|
|
|
|
|
|
Earth cable |
| 16 |
| 16 |
| 25 |
| 25 |
|
|
|
|
|
|
|
|
|
3.1.3 Selection of signal cables
Signal cables should use shielded
mm.Serial communication cables should use 3 or 5 shielded conductor cables.
3.2Cable connections
3.2.1Power cables
1.Cabling layout
Cabling layout is shown in Figures
24