| Chapter 10 | Service after Sales |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
| No.1 |
| Fault description |
|
| Reason |
|
| Actions to be taken |
|
| ||||||||
|
|
|
|
|
|
| The battery life is reduced due to |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| aging, which may endanger the |
| Notify the service dept for replacing the | ||||||||||
| 16 |
| Battery needs to be |
|
| normal operation of UPS. Warn |
| battery and set the battery model and | |||||||||||
|
|
| replaced |
|
|
| the user that the battery is |
| parameters through software. |
|
| ||||||||
|
|
|
|
|
|
| abnormal and needs to be |
|
|
| |||||||||
|
|
|
|
|
|
| replaced. |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
| 17 |
| No battery |
|
| Batteries are not connected. | Check | the | battery and | the | wiring | of | |||||||
|
|
|
|
|
|
|
| batteries |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| The battery discharges to pre- |
|
|
|
|
|
|
|
|
|
| ||
| 18 |
|
|
| alarm point(the battery capacity |
| Shut down the load in time |
|
|
| |||||||||
|
| battery discharging |
|
| is inadequate),the system may |
|
|
|
| ||||||||||
|
|
|
|
|
|
| shut down after a few minutes |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| 19 |
| battery over temperature | battery temperature is too high |
| Check | the | battery | temperature | and | |||||||||
|
|
| ventilation |
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||||||||||||
| 20 |
| battery |
| The battery condition for |
| Start the self test after the conditions | ||||||||||||
|
|
|
|
|
|
| is not satisfied |
| can meet the requirements |
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
| 21 |
| Battery is connected |
|
| Battery is connected reverse |
| Notify | the | UPS service | engineer | to | |||||||
|
| reverse |
|
|
|
| connect the battery again |
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
| 22 |
| Bypass | phase rotation is |
| Bypass phase rotation is reverse | Notify | the | UPS service | engineer | to | ||||||||
|
| reverse |
|
|
|
|
|
|
| change the bypass phase rotation |
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
| 23 |
| Rectifier | heatsink | over |
| Rectifier | heatsink temperature is |
| The UPS | can | recover | automatically. | ||||||
|
| temperature |
|
| too high |
|
|
| Check the environment and ventilation | ||||||||||
|
|
|
|
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
| 24 |
| Rectifier fan fails |
|
| Rectifier fan is abnormal |
| Replace the fan in time and the UPS | |||||||||||
|
|
|
|
| can recover automatically |
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| Inverter | is | asynchronous with |
| Check if the bypass is normal. The fault | ||||||||
| 25 |
| Inverter asynchronous |
|
|
| alarm | stops automatically | after |
| the | ||||||||
|
|
|
|
|
|
| bypass |
|
|
| bypass recovers normal |
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
| 26 |
| Inverter | heatsink | over |
| Inverter | heatsink temperature is |
| The UPS | can | recover | automatically. | ||||||
|
| temperature |
|
| too high |
|
|
| Check the environment and ventilation | ||||||||||
|
|
|
|
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
| 27 |
| Inverter fan fails |
|
| Inverter fan is abnormal |
| Replace the fan in time and the UPS | |||||||||||
|
|
|
|
| can recover automatically |
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| The IGBT of inverter has over |
| Restart the inverter, if the fault can’t be | ||||||||||
| 28 |
| Inverter over current |
|
| current resulting in the shut down |
| cleared, notify the service dept for | |||||||||||
|
|
|
|
|
|
| if inverter. |
|
| repairing. |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
| Check whether there is fault in rectifier | ||||||||
| 29 |
| Shutdown due to low bus |
| DC bus voltage is too low result in |
| side, | if no, | then | check whether | |||||||||
|
| voltage |
|
|
| the shutdown of inverter |
| overload occurs. Restart after clearing | |||||||||||
|
|
|
|
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
| the fault. |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| ||||||||||
| 30 |
| Output | transformer | over |
| Output transformer temperature is |
| Auto recovery, ambient and ventilation | ||||||||||
|
| temperature |
|
| too high |
|
|
| of UPS should be checked. |
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
| 31 |
| Overload of single UPS | Load is too heavy |
| Disconnect | unnecessary | load | and | ||||||||||
|
|
| ensure the safety. |
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| 32 |
| Overload of system |
| System load is too heavy |
| Disconnect | unnecessary | load | and | |||||||||
|
|
|
| ensure the safety. |
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| 33 |
| Overload exceeds normal |
| Over load | occurs in inverter |
| If the load decreases after 5 minutes, | |||||||||||
|
| time |
|
|
| mode, transfers to bypass mode |
| the system will back to inverter mode | |||||||||||
|
|
|
|
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
114