Chapter 9 Optional Parts

Chapter 9 Optional Parts

9.1 Battery

9.1.1 Capacity selection

Calculate the discharging current according to rated load capacity and then select the battery according to the current and the battery backup time required by user. There are various specifications of battery, we recommend that 30 12V battery cells should be connected in series to form a battery string. The capacity of battery cell can be 38Ah, 65Ah and 100Ah.

Note

If the battery capacity exceeds 100Ahthe user should connect the battery of

same model and same capacity in parallel or use large capacity 2V battery to make up the battery group.

The capacity data of battery string are listed in Table 9-2 and the capacity data are selected according to rated load. Select the battery of 70%~100% rated capacity according to the actual load and required backup time.

Table 9-1 Battery capacity equipped for single UPS (Ah25)

 

UPS

20kVA

30kVA

40kVA

60kVA

 

capacity

 

 

 

 

 

 

 

 

 

 

 

 

Discharging

50A

75A

100A

150A

 

current

 

 

 

 

 

 

 

 

 

 

 

 

Backup time

 

Battery capacityAh

 

 

 

 

 

 

 

 

15min

38

65

100

100

 

 

 

 

 

 

 

30min

65

65

100

150

 

 

 

 

 

 

 

1h

100

130

180

340

 

 

 

 

 

 

 

2h

150

200

340

420

 

 

 

 

 

 

 

3h

200

340

420

630

 

 

 

 

 

 

 

4h

250

340

510

680

 

 

 

 

 

 

 

5h

340

420

630

840

 

 

 

 

 

 

 

6h

340

510

680

1020

 

 

 

 

 

 

 

8h

420

630

840

1260

 

 

 

 

 

 

101

Page 107
Image 107
Liebert UPS System user manual Battery, Capacity selection