Chapter 4 Commissioning of UPS

UL33-0400L 2001-11-08

12:50:30

 

Inv. On

Units 2/4

ID: 1

 

Out

Comm. Mode Set

RS232

 

Local

MODEM

RS232

 

 

System

Comm. Baudrate Set 9600

 

Battery

9600

4800 2400

1200

 

Records

Callback Times Set

3

 

3

 

 

 

 

Settings

 

 

 

 

Input Breaker Closed 11£ -08 12:09

 

Byp. Breaker Closed 11£ -08 12:09

 

Mains Volt. Abnormal

11£ -08 12:28

m

UPS in Battery Mode

11£ -08 12:28

 

Battery low

11£ -08 12:50

 

Fig. 4-5 Background Communication

Callback number 1 : the first callback number can be a mobile phone number, a fixed line phone number, a beeping pager or an extension telephone. The length of the telephone number is 15 digits. Input the number from the first digit and any remaining blanks digits has to be entered with an asterisk “*”

Callback number 2 : same as for callback number 1

Callback number 3 : same as for callback number 1

UL33-0400L 2001-11-08

12:50:30

Inv. On

Units 2/4

ID: 1

Out

Comm. Mode Set

RS232

Local

MODEM RS232

 

System

Comm. Baudrate Set 9600

Battery

9600 4800 2400

1200

Records

Callback Times Set 3

3

 

Settings

 

Input Breaker Closed 11£ 08-

12:09

Byp. Breaker Closed 11£ 08- 12:09

Mains Volt. Abnormal

11£ 08-

12:28

UPS in Battery Mode

11£ -08

12:28

Battery low

11£ -08

12:50

m

Fig. 4-6 Fault Call-back

4.3 Functional checks

Check the functions of switching between operation modes, visual and audible alarms and the display functions.