Chapter 4 Commissioning of UPS
12:50:30 |
| |||||
Inv. On | Units 2/4 | ID: 1 |
| |||
Out | Comm. Mode Set | RS232 |
| |||
Local | MODEM | RS232 |
|
| ||
System | Comm. Baudrate Set 9600 |
| ||||
Battery | 9600 | 4800 2400 | 1200 |
| ||
Records | Callback Times Set | 3 |
| |||
3 |
|
|
|
| ||
Settings |
|
|
|
| ||
Input Breaker Closed 11£ |
| |||||
Byp. Breaker Closed 11£ |
| |||||
Mains Volt. Abnormal | 11£ | m | ||||
UPS in Battery Mode | 11£ | |||||
| ||||||
Battery low | 11£ |
|
Fig. 4-5 Background Communication
Callback number 1 : the first callback number can be a mobile phone number, a fixed line phone number, a beeping pager or an extension telephone. The length of the telephone number is 15 digits. Input the number from the first digit and any remaining blanks digits has to be entered with an asterisk “*”
Callback number 2 : same as for callback number 1
Callback number 3 : same as for callback number 1
12:50:30 | ||
Inv. On | Units 2/4 | ID: 1 |
Out | Comm. Mode Set | RS232 |
Local | MODEM RS232 |
|
System | Comm. Baudrate Set 9600 | |
Battery | 9600 4800 2400 | 1200 |
Records | Callback Times Set 3 | |
3 |
| |
Settings |
|
Input Breaker Closed 11£ 08- | 12:09 | |
Byp. Breaker Closed 11£ 08- 12:09 | ||
Mains Volt. Abnormal | 11£ 08- | 12:28 |
UPS in Battery Mode | 11£ | 12:28 |
Battery low | 11£ | 12:50 |
m
Fig. 4-6 Fault Call-back
4.3 Functional checks
Check the functions of switching between operation modes, visual and audible alarms and the display functions.
40