Chapter 1 Introduction

4. ECO Mode

If the load has no requirement for power quality but has a high requirement for efficiency, then the UPS can be set in ECO mode. In this mode, the system will power the load through the static bypass switch and the rectifier will charge the batteries. When the bypass source fails or out of normal range, the UPS will revert back to normal mode and powers the load through the batteries. The total transfer time will be less than 15 msecs. When the bypass source recovers back to normal, the system will return to ECO mode automatically and the system efficiency is greatly improved, as shown in Figure 1-8. Note that the ECO mode function can only be set by qualified personnel and applies to single UPS modules only.

Bypass

Mains ~ -

- ~ output

Figure 1-8 ECO mode

5. Maintenance Mode

When the UPS has to be repaired or has to undergo routine maintenance, the UPS can be set to maintenance mode by switching on the maintenance bypass circuit breaker. The load will be powered from the maintenance bypass supply without interruption.

During maintenance, the circuit breakers Q1, Q2, QF1 and Q5 should be switched off to ensure the safety of maintenance personnel. See Figure 1-9.

 

 

Q3BP

 

 

 

Bypass

Q2

 

 

 

 

 

 

 

Mains

Q1

~ -

-

Q5

Output

 

 

~

 

 

 

 

QF1

 

 

Figure 1-9

6

Page 12
Image 12
Liebert UPS System user manual ECO Mode, Maintenance Mode