Chapter 1 Introduction

 

Capacity

 

20kVA

 

30kVA

 

40kVA

60kVA

 

 

 

 

 

 

 

 

 

 

Model

 

UL33-0200L

UL33-0300L

 

UL33-0400L

UL33-0600L

 

 

 

 

 

 

 

 

 

 

 

 

105% < load 125% , transfer to bypass mode after 10±0.1min;

 

Overload capability(inverter)

125% < load 150% , transfer to bypass mode after 1 minute;

 

 

 

 

When load > 150%, transfer to bypass mode after 200ms

 

 

 

 

 

 

 

 

 

 

135% Rated Current continuously

 

 

 

 

 

135%~170% for 1 minute

 

 

 

Output

Overload capability(bypass)

>170%, shutdown in 2s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1000% rated current for 20ms(a standard for selecting static

 

 

 

 

switch)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ratio of output

current peak

3: 1

 

 

 

 

 

 

value to RMS value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transfer time(normal mode)

0(uninterrupted transfer)15ms(interrupted transfer)

 

 

 

 

 

 

 

 

 

Transfer time(ECO mode)

15ms

 

 

 

 

 

 

 

 

 

 

 

 

System

System efficiency(linear load)

87%

 

87%

 

88%

89%

 

 

 

 

 

 

 

 

 

 

Efficiency in battery

92%

 

93%

 

93%

94%

 

mode(linear load)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Display

LCD+LED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Conduction

EN50091-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Radiation

EN50091-2 CLASS-A

 

 

 

 

 

 

 

 

 

 

 

 

 

EMC/EMI

 

Harmonic

IEC1000-3-4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Immunity

EN 61000-4-2.3.4..6.8.9.11

Level III,

 

 

 

 

EN 61000-4-5

Level

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MTBF(inverter)

 

30,000 hours

 

 

 

 

 

 

 

 

 

 

 

 

MTBF(Single UPS)

150,000 hours

 

 

 

 

 

 

 

 

 

 

 

 

 

MTBF(1+1 parallel operation

400,000 hours

 

 

 

 

 

system)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Safety

 

CCEE

 

 

 

 

 

 

 

 

 

 

 

 

Audible noise at 2m

<60dB

 

 

 

<65dB

 

 

 

 

 

 

 

 

 

Cross current without

<3A

 

 

 

 

 

load(1+1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cross current without

<4A

 

 

 

 

 

load(3+1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

current unbalance rate(1+1)

<3%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

current unbalance rate(3+1)

<4%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

Page 16
Image 16
Liebert UPS System user manual Lcd+Led