Chapter 7 Troubleshooting
| No.1 |
| Fault description |
| Reason |
| Actions to be taken |
|
|
|
|
| The system transfers to bypass |
|
|
| 49 |
| Transfer to bypass |
| mode due to surge current and back |
| Avoid applying load abruptly and the UPS |
|
| due to surge |
| to inverter mode after load is |
| can recover automatically | |
|
|
|
|
| |||
|
|
|
|
| decreased |
|
|
|
|
|
|
|
|
|
|
|
|
| User’s wrong |
| Wrong operation such as start the |
|
|
| 50 |
|
| UPS with the maintenance bypass |
| Operate with reference to User’s Manual | |
|
| operation |
|
| |||
|
|
|
| switched on |
|
| |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| The actual transfer |
| Transfer times exceed the times set |
|
|
| 51 |
| times exceed the |
| by background. The system will stay |
| Avoid frequent overload |
|
|
| permissible transfer |
| in bypass mode until next hour. |
|
|
|
|
| times per hour |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
| Table | operation system |
| No. |
| Fault description |
|
| Reasons |
|
| Fault processing | |||
| 1 |
| Overload | of | parallel |
| Overload | occurs and | the |
| Disconnect the load of low priority, maintain the | |
|
| operation system |
| redundancy is not available |
| power supply to important load | ||||||
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
| In parallel operation system, |
|
| |||
|
|
|
|
|
|
| some UPS | module | may |
|
| |
|
|
| Neighbouring | UPS |
| require to transfer to bypass |
| If the parallel operation system transfers to | ||||
| 2 |
| module | requires to |
| due to surge or overload, |
| bypass mode, and the operation condition | ||||
|
| transfer | to | bypass |
| other modules will transfer to |
| enables, all the UPS modules can recover to | ||||
|
|
| mode |
|
|
| bypass | after | receiving | the |
| normal mode synchronously. |
|
|
|
|
|
|
| signal sent by this UPS |
|
| |||
|
|
|
|
|
|
| module | that | requires | to |
|
|
|
|
|
|
|
|
| transfer to bypass mode |
|
|
| ||
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
| The load current of each UPS |
|
| |||
| 3 |
| Load sharing fault |
| module is noticeably |
|
| Notify the service dept for repairing | ||||
|
|
| unbalanced, thus the system |
| ||||||||
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
| loading ability is affected. |
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| ||
| 4 |
| Parallel operation |
| The board is damaged. |
|
| Notify the service dept for repairing | ||||
|
| board fails |
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
86