Chapter 7 Troubleshooting

 

No.1

 

Fault description

 

Reason

 

Actions to be taken

 

 

 

 

 

The system transfers to bypass

 

 

 

49

 

Transfer to bypass

 

mode due to surge current and back

 

Avoid applying load abruptly and the UPS

 

 

due to surge

 

to inverter mode after load is

 

can recover automatically

 

 

 

 

 

 

 

 

 

 

decreased

 

 

 

 

 

 

 

 

 

 

 

 

 

User’s wrong

 

Wrong operation such as start the

 

 

 

50

 

 

UPS with the maintenance bypass

 

Operate with reference to User’s Manual

 

 

operation

 

 

 

 

 

 

switched on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The actual transfer

 

Transfer times exceed the times set

 

 

 

51

 

times exceed the

 

by background. The system will stay

 

Avoid frequent overload

 

 

 

permissible transfer

 

in bypass mode until next hour.

 

 

 

 

 

times per hour

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 7-2 Fault of parallel

operation system

 

No.

 

Fault description

 

 

Reasons

 

 

Fault processing

 

1

 

Overload

of

parallel

 

Overload

occurs and

the

 

Disconnect the load of low priority, maintain the

 

 

operation system

 

redundancy is not available

 

power supply to important load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In parallel operation system,

 

 

 

 

 

 

 

 

 

some UPS

module

may

 

 

 

 

 

Neighbouring

UPS

 

require to transfer to bypass

 

If the parallel operation system transfers to

 

2

 

module

requires to

 

due to surge or overload,

 

bypass mode, and the operation condition

 

 

transfer

to

bypass

 

other modules will transfer to

 

enables, all the UPS modules can recover to

 

 

 

mode

 

 

 

bypass

after

receiving

the

 

normal mode synchronously.

 

 

 

 

 

 

 

signal sent by this UPS

 

 

 

 

 

 

 

 

 

module

that

requires

to

 

 

 

 

 

 

 

 

 

transfer to bypass mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The load current of each UPS

 

 

 

3

 

Load sharing fault

 

module is noticeably

 

 

Notify the service dept for repairing

 

 

 

unbalanced, thus the system

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

loading ability is affected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

Parallel operation

 

The board is damaged.

 

 

Notify the service dept for repairing

 

 

board fails

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

86