Chapter 2

Installation and Setup

This chapter provides instructions for mechanical and electrical installation of the FCD-IPM unit.

After installation, you must configure the unit before further operation. Refer to Chapter 4 for basic and advanced configuration instructions. In case a problem is encountered, refer to Chapter 5 for test and diagnostics instructions.

No internal settings, adjustment, maintenance, and repairs may be performed by either the operator or the user; such activities may be performed only by a

skilled technician who is aware of the hazards involved. Always observe

standard safety precautions during installation, operation, and maintenance of Warning this product.

2.1 Site Requirements & Prerequisites

Install AC powered FCD-IPM units within 1.5m (5 feet) of an easily accessible, grounded AC outlet capable of furnishing the nominal supply voltage, 115 or 230 VAC. DC powered units require a 24 or -48 VDC power source.

Allow at least 90 cm (36 inches) of frontal clearance for operator access. Allow at least 10 cm (4 inches) clearance at the rear for interface cable connections. The ambient operating temperature of FCD-IPM is 0° to 50°C (32° to 122°F), at a relative humidity of up to 90%, non-condensing.

Note

The FCD-IP units are cooled by free air convection therefore in rack installation it is

 

necessary to leave sufficient space (at least 1U) above and below each unit to

 

enable free airflow.

Site Requirements & Prerequisites

2-1

Page 37
Image 37
RAD Data comm Modular Access Device with Integrated Router, E1/T1 Site Requirements & Prerequisites, Enable free airflow