From the previous page

Writing to the EEPROM of the JW-20CM, start operation [HEX (hexadecimal), byte]

·Write “81(H)” into parameter address 007777(8) and write the set parameter contents into the EEPROM of the JW-20CM. Then start the JW-20CM.

·After starting operation, the setting value changes to “01(H).”

Setting

Contents

value (H)

0 0

Stop operation of the JW-20CM

 

 

0 1

Start operation of the JW-20CM

 

 

8 0

Writing to the EEPROM of the JW-20CM, stop operation

 

 

8 1

Writing to the EEPROM of the JW-20CM, start operation

 

 

0 8

Initialize parameters

 

 

Screen display of JW-13PG

 

 

07775

HEX

00

Display the contents of address

Write 81(H)

07776

HEX

EC

I PARAM.

 

 

007777(8)

 

 

 

>07777

HEX

81

 

 

Remarks留 意 点

·Writing time to EEPROM is approximately 0.7 sec. When any error is found for parameter settings, the JW-20CM lights the error code (6F(H)) by the indication lamp.

When error code 6F(H) lights,

9

Check flag top address

If the master station also lights up with error code 6F(H), check the top address and number of bytes in the relay link and register link in the master station which corresponds to the slave station in which the error occurred.

·Written contents into the EEPROM are automatically transferred to the RAM of the JW-20CM when turning ON the power of the PC. At transferring, the PC checks BCC and compares BCC check code of the parameter memory address (007776(8)). When an error is found, the JW-20CM lights the error code (6E(H)) by the indication lamp.

·If "parameter initialization" is selected, the module initializes parameter addresses 004000 to 007776(8).

PC operation

Turning a slave module to monitor or change mode (PC operation). (Operation example of using JW-13PG)

Monitor mode

Screen display of JW-13PG

 

 

 

Change mode

 

 

 

C00000

 

 

 

>

 

 

 

 

 

9·32