(4)Voltage interruption time of slave module

The voltage interruption operation of slave module is carried out for service interruption signal (PF signal) of power supply module, watchdog timer of slave module, and check 5 V power regardless of setting voltage interruption time (#246) of master module.

 

 

Start

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PF signal OFF

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Communicating

Yes

 

 

 

 

at remote I/O

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I/O processing of I/O module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

Output

 

 

 

hold RST

 

 

 

 

 

 

switch

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

Yes

 

Watchdog timer

 

 

 

 

 

 

 

 

 

 

 

 

time-up

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

5V power 4.5V max.

 

No

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Halt output “open”

 

 

 

 

 

 

All output module “OFF”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

·The PF signal of the power supply module goes “OFF” below 85% of the rated voltage.

·The watchdog timer of the slave module goes time-up in “320 ms.”

·When output hold switch is “RST,” the all halt output and output module become “OFF” when communication with master station have interruption of 320 ms.

End

·When the check of 5 V power is gone below 4.5 V, all are forced to reset. The power supply characteristics varies according to the consumption current of the power supply module as following diagrams.

 

120

 

 

 

 

 

 

Output hold time

 

100

 

 

5.1V,7A load

 

 

 

[ms]

 

 

(ZW-1PU)

 

 

 

 

 

 

5.1V,5A load

Hold time

 

 

 

80

 

 

(ZW-2PU)

60

 

 

 

 

 

 

 

 

40

 

 

 

 

20

 

 

 

 

0

 

 

 

 

 

 

 

85V/170V

100V/200V

120V/240V

132V/264V

 

 

AC input voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20V

24V

28V

32V

DC input voltage

Hold time [ms]

 

 

 

 

Output hold time

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

280

 

 

 

 

100 VAC 50H input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(ZW-1PU)

 

 

 

 

240

 

 

 

 

24 VDC input

 

 

 

 

 

 

 

 

(ZW-2PU)

 

 

 

 

200

 

 

 

 

 

 

 

 

 

 

160

 

 

 

 

 

 

 

 

 

 

120

 

 

 

 

 

 

 

 

 

 

80

 

 

 

 

 

 

 

 

 

 

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

1

2

3

4

5

6

7

 

 

 

 

 

 

 

 

 

Load current [A]

8·7