"Only when using fixed allocation"

Enter the number of slave station I/O points

[HEX (hexadecimal), bytes]

 

 

 

(Applied to item on pages 8·31 and 8·35)

·Store the number of I/O points per slave station at parameter address 000200(8).

·The number of slave stations that can be connected varies with the setting for the number of I/O points per slave station.

Set value

Number of I/O points

Number of modules that

 

can be connected.

 

 

 

 

00(H)

64 points/station

0 to 63(D)

Initial value: 00(H)

 

 

 

 

01(H)

128 points/station

0 to 32(D)

 

 

 

 

 

·Allocates the number of I/O points per slave station as 64 points per unit or 128 points per unit, starting from the top address set by the procedure on the previous page.

Ex.: When a remote I/O's top address is 0200 and the number of slave station I/O points is 64.

 

 

0200 Remote I/O top address

(64 points)

Slave station 01

0210

 

 

(64 points)

Slave station 02

0220

 

 

(64 points)

Slave station 03

0230

 

 

(64 points)

Slave station 04

0240

 

 

 

 

(When set for 64 points per station using the JW-13PG)

Screen display of JW-13PG

8

Write

00176

HEX

00

Display the contents of

00177

HEX

00

address 000200(8)

00(H)

I PARAM.

HEX

00

 

 

>00200

8·38