From the previous page

Data link function setting [HEX (hexadecimal), byte]

 

 

 

 

 

 

 

 

 

 

 

• Set “01(H) (=001(8))” in parameter address 004002(8) and change to “relay/register link.”

 

 

 

 

 

 

 

Screen display of JW-13PG

 

(Operation example of JW-13PG)

 

 

 

 

 

 

 

 

 

 

 

04000

HEX

880

 

 

 

 

 

 

 

04001

HEX

00F

 

 

 

Write 001(8)

to 004002(8)

 

I PARAM.

 

 

 

 

 

 

>04002

HEX

01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set number of connecting stations

[DCM (decimal), byte]

 

 

 

 

 

Set the number of connecting stations (02 to 64(D)) including the master station in the parameter address 004003(8) by octal.

If you try to set values other than 02 to 64(D), JW-20CM the displays 6F(H) error code.

Screen display of JW-13PG

After converting into decimal

04001

DCM

000

04002

DCM

001

notation in 004003(8), write “003.”

I PARAM.

 

 

>04003

DCM

003

 

 

 

 

 

Set top address of relay link area on slave station (01 to 77) (at standard function)/number of offset bytes (memory capacity save function)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

File address: OCT (octal), word

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

File number/flag: HEX (hexadecimal), byte

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set the "same" as or "different" from the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

master station: HEX (hexadecimal) , bytes.

 

 

 

• Set in parameter addresses 004004 to 004377(8). These top addresses should not overlap the

9

register link area, flag area, or any area used by other option module.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In case of standard function, set top address by file address(8).

 

Slave

 

 

 

004004(8)

Lower

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

004005(8)

Upper

 

 

 

 

In case of save memory function, set number of offset bytes.

 

station

 

 

 

 

 

004006(8)

00(H)

 

 

 

 

 

 

 

 

 

 

01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

004007(8)

·

 

 

 

 

 

00(H): The top address is the same address of the master station

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

regardless of the value set at of 004004 to 004005(8).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80(H): The top address is different from the address of the master

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

station (Offset is valid).

 

Slave

 

 

004374(8)

Lower

 

 

 

 

For the save memory function, set in 80(H).

 

 

 

 

 

 

 

 

 

004375(8)

Upper

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

station

 

 

 

 

 

 

 

 

 

 

 

 

004376(8)

00(H)

 

 

 

 

 

 

 

 

 

 

77(8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

004377(8)

·

 

 

 

 

 

 

00(H)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80(H)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In case of setting 0200 (file address 000200(8)) in parameter addresses 004004 to 004007(8) (slave station 01) and set 4 (number of off set bytes) in 004010(8) to 004013(8) (slave station 02). (Example for page 11·10.)

To the next page