During initial communication (start-up of the system)Lighting error code 6F(H)

·When the master station indicates error code 6F(H) and the COMM lamp is OFF.

The cause may be a parameter setting error of the master station. Check the master station parameters below.

Parameter address(8)

Contents

Setting range

 

 

 

004000 to 004001

Relay link top address of master

0000 to 39777(8)

station

(File 0 : 000000 to 007777(8))

 

 

 

 

004003(8)

Amount of connectable stations

2 to 64(D)

 

 

 

 

Register link top address of

0000 to 99777(8)

004400 to 004403

(File 0 : 000000 to 015777(8))

master station

000000 to 177777(8)

 

 

 

(File 1 to 7)

 

 

 

005000 to 005177(8)

Relay link sending bytes of each

0 to 256D)

station

Total : 256 max.

 

 

 

 

005200 to 005377

Register link sending bytes of

0 to 2048(D)

each station

Total : 2048 max.

 

 

 

 

 

 

0000 to 99777(8)

007764 to 007767

Flag top address

(File 0 : 000000 to 015777(8))

000000 to 177777(8)

 

 

 

 

(File 1 to 7)

 

 

 

·When the master station indicates error code 6F(H) and the COMM lamp lights.

The cause may be a setting error of any of the slave stations which are set in the parameter. Check the following master station parameters.

 

 

Parameter address(8)

Contents

Setting range

9

 

 

 

 

 

 

Relay link top address of slave

0000 to 39777(8)

 

 

004004 to 004377

station

(File 0 : 000000 to 007777(8))

 

 

 

 

 

 

Relay link offset bytes of slave

00000 to 00256(D)

 

 

 

 

 

 

station

 

 

 

 

 

 

 

 

 

 

 

 

Register link top address of slave

0000 to 99777(8)

 

 

 

(File 0 : 000000 to 015777(8))

 

 

004404 to 004777

station

000000 to 177777(8)

 

 

 

(File 1 to 7)

 

 

 

 

 

 

 

 

 

 

 

 

Register link offset bytes of slave

00000 to 02048(D)

 

 

 

station

 

 

 

 

 

 

 

 

 

 

 

005000 to 005177

Relay link top address sending

0 to 256D)

 

 

bytes of each station

Total : 256 max.

 

 

 

 

 

 

 

 

 

 

005200 to 005377

Register link sending bytes of

0 to 2048(D)

 

 

each station

Total : 2048 max.

 

 

 

 

 

 

 

 

 

 

 

 

0000 to 99777(8)

 

 

007764 to 007767

Flag top address

(File 0 : 000000 to 015777(8))

 

 

000000 to 177777(8)

 

 

 

 

 

 

 

 

(File 1 to 7)

 

 

 

 

 

When slave station is JW-22CM, see “JW-22CM users manual” for setting range.

9·66