(3)Specifications of each functionSpecifications of remote I/O slave station

Item

 

Specification

 

 

 

No. of remote I/O slave station

63 sets max.

 

 

 

 

Total no. of remote I/O points

4096 points max.

 

 

 

 

 

 

Per station 64 points : Total of 63 stations

 

Fix allocation

4032 points

 

 

No. of remote I/O points

Per station 128 points : Total of 32

 

 

stations 4096 points

 

 

 

 

 

 

Manual allocation

Per station 8 to 1024 points : Total of

 

4096 points

 

 

 

 

 

 

Operation synchronous

Communicates synchronously with the

Synchronous method with PC

PC's I/O processing cycle.

 

operation

Operation asynchronous

Communicates separate with the PC's

 

 

 

I/O processing cycle.

Data link specifications

 

Item

Specification

 

 

 

 

 

 

 

 

Relay link

Register link

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No. of data link stations

64 sets max.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ZW-PC

File 0

 

 

 

 

 

 

(000000 to 005777(8))

File 0 (000000 to 015777(8))

 

 

 

Link area

 

 

 

JW-PC

File 0

File 1 to 7 (000000 to 177777(8))

 

 

 

 

 

 

 

(000000 to 007777(8))

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total no. of link points

2048 points max.

2048 bytes max.

 

 

 

(256 bytes)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total no. of

Standard function

2048 points max.

2048 bytes max.

 

 

 

sending/receiving

(256 bytes)

 

 

points per slave

Memory capacity

512 points max.

512 bytes max.

 

 

 

station

save function

(64 bytes)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Communication mode

N:M communication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Computer link specifications

 

 

 

 

12

 

 

 

 

 

Item

Specification

 

 

 

 

 

 

 

 

 

 

 

No. of link stations

64 sets max.

 

 

 

 

 

 

 

 

 

Communication data size

1024 bytes max./packet *

 

 

 

 

 

 

Communication control

According to the host computer command

 

 

 

 

 

 

 

 

 

Read/write of data memory

 

 

Control contents

 

Read/write of program memory

 

 

 

 

PC control

 

 

 

 

 

 

 

 

 

 

 

 

*The amount of data attributed to the command, or response. The term "packet" refers to the value for each station.

12·3