From the previous page

Writing to the EEPROM of the JW-20CM, start operation

[HEX (hexadecimal), byte]

 

 

·Write “81(H)” into parameter address 003777(8) and write the set parameter contents into the EEPROM of the JW-20CM. Then start the remote I/O operate.

·After starting operation, the setting value changes to “01(H).”

Setting

Contents

value (H)

0 0(H)

Stop operation of the remote I/O (initial value)

·Calculate BCC of parameter addresses 000000 to 003775(8).

0 1 When normal, the remote I/O will start operation.

When abnormal, the module will output error code BE(H).

Check the parameter contents

When normal, the module calculates BCC and writes the check sum

value into address 003776(8).

When abnormal, it outputs a BF(H) error code.

8 0(H) Changes the value to 00(H) (stops the operation of the remote I/O), and writes it into the EEPROM.

If a write error to the EEPROM occurs, it outputs a 30(H) error code and keeps the value set to 80(H).

Writing to the EEPROM of the JW-20CM, start operation

Check the parameter contents

When normal, the module calculates BCC and writes the check sum value into address 003776(8).

When abnormal, it outputs a BF(H) error code.

8 1(H) Changes the value to 01(H) (starts the operation of the remote I/O), and

writes it into the EEPROM.8 If a write error to the EEPROM occurs, it outputs a 30(H) error code and

keeps the value set to 81(H).

Writing to the EEPROM of the JW-20CM, start operation

0 8 Initialize setting values of parameter addresses 000000 to 003777(8)

(Operation example of JW-13PG)

Screen display of JW-13PG

 

03775

HEX

00

 

03776

HEX

00

Display the contents of address

I PARAM.

 

 

>03777

HEX

01

003777(8)

Write 81(H)

 

 

 

 

 

PC operation

Turning a master station PC to monitor or change mode (PC operation).

(Operation example of JW-13PG)

Monitor mode

Change mode

8·37