9-8 Error and treatment

Operation status of the JW-20CM can be check by indication lamps, flags, or system memory.

(1) Indication lamp

JW–20CM

C O M M

S 0

S D

S 1

R D

S 2

C D

S 3

L T

S 4

T E S T

S 5

E R R O R

S 6

F A U L T

S 7

Indication lamp

Name

Operation

Recovery

9

COMM

Lights while the remote I/O is operating

--------------------------------------------------

 

SD

Flickers while sending data

--------------------------------------------------

 

RD

Flickers while receiving data

--------------------------------------------------

 

CD

Flickers while detecting a carrier

--------------------------------------------------

 

 

Lights when the termination resistance

 

 

LT

 

--------------------------------------------------

 

 

switches turned ON

 

 

TEST

Lights while testing

--------------------------------------------------

 

 

 

· Check disconnection of communication cable

 

 

Lights while an error is detected (Indicate

· Check settings of switches

 

ERROR

 

 

 

 

error code by S0 to S7 LEDs)

· Check settings of parameter

 

 

 

· Check power supply voltage.

 

 

Lights when the watchdog timer is time

 

 

FAULT

 

Replace the JW-20CM

 

 

up (JW-20CM is faulty)

 

 

 

Indicates error codes by hexadecimal

 

 

S0 to S7

 

See the next page

 

 

when an error is occurred

 

 

9·53