Setting parameter

After finishing communication with the target station, set the parameters remotely.

Return to initial menu.

Turn the PC of the target station to program mode (stop PC operation).

Select “PARAM.” in the initial mode.

<<In case of remote I/O function>>

Display contents of parameter address 003777(8).

Write in 00(H), stop operation of the JW-20CM.

<<In case of data link function>>

Display contents of parameter address 007777(8).

Write in 00(H), stop operation of the JW-20CM.

Input address

Display contents of address to set the parameters.

Input setting value

Setting parameter remotely.

Writing to the EEPROM, start operation

After setting the parameter remotely in step , write 81(H) at parameter address 003777(8) (when at remote I/O function), or at 00777(8) (when at data link function), to start the "writing operation to EEPROM."