“Run” the slave station PCTurn “ON” the power of the master station PC and connect support tools

• Connect a support tool with the JW-20CM and prepare the setting parameter.

<Usable support tools> JW-13PG/12PG JW-50SP JW-50PG, Z-100LP2S

For operation of each support tool, see the instruction manual attached. The following describes an example of JW-13PG’s key operation.

Stop PC operation

Turn to program mode (stop PC operation). Setting of parameters is only available when the PC is in program mode.

(Operation example of JW-13PG)

 

Stop PC operation

 

 

Select parameter setting mode.

 

Select initial mode

Parameter

 

setting

 

Stop operation of data link

[HEX (hexadecimal), byte]

9

Setting of the parameter is only available when the operation of the JW-20CM is stopped.

Write “00(H)” to parameter address 007777(8) and stop operation of the JW-22CM.

(Operation example of JW-13PG)

Screen display of JW-13PG

 

 

 

 

 

 

07775

HEX

00

 

Display the contents of parameter

Write

 

07776

HEX

00

 

00(H).

I PARAM.

 

 

 

address 007777 by hexadecimal.

>07777

HEX

00

 

 

Function of JW-13PG

 

 

 

 

 

Reference

 

 

 

 

 

key: Changeover unit of figures

 

 

 

 

 

 

 

HEX(hexadecimal) OCT(octal) DCM(decimal) Bit pattern

 

 

 

 

 

 

 

key: Byte display ←→ Changeover word display

To the next page

9·39