| Table 1 — Unit Sizes | |
|
|
|
UNIT |
| NOMINAL CAPACITY |
| (TONS) 50/60 Hz | |
|
| |
30RA010 |
| 10/10 |
30RA015 |
| 14/13 |
30RA018 |
| 16/16 |
30RA022 |
| 22/20 |
30RA025 |
| 24/23 |
30RA030* |
| 27 |
30RA032† |
| 30 |
30RA035 |
| 35/34 |
30RA040* |
| 38 |
30RA042† |
| 40 |
30RA045 |
| 43/45 |
30RA050* |
| 47 |
30RA055* |
| 54 |
*60 Hz only. †50 Hz only.
MAJOR SYSTEM COMPONENTS
General — The 30RA
The control system is composed of several components as listed in the sections below. See Fig. 1 and 2 for typical control box drawing. See Fig.
Main Base Board (MBB) — See Fig. 7. The MBB is the heart of the ComfortLink control system. It contains the major portion of operating software and controls the operation of the machine. The MBB continuously monitors input/output channel information received from its inputs and from all other modules. The MBB receives inputs from the discharge and suction pressure transducers and thermistors. See Table 2. The MBB also receives the feedback inputs from each compressor contactor, auxiliary contacts, and other status switches. See Table 3. The MBB also controls several outputs. Relay outputs controlled by the MBB are shown in Table 4. Information is transmitted between modules via a
Scrolling Marquee Display — This standard device is the keypad interface used for accessing chiller information, reading sensor values, and testing the chiller. The marquee display is a
Energy Management Module (EMM) — The EMM module is available as a
Enable/Off/Remote Contact Switch — The Enable/ Off/Remote Contact switch is a
Contact (dry contacts closed) positions, the chiller is allowed to operate and respond to the scheduling configuration, SCN configuration and set point data. See Fig. 8.
Emergency On/Off Switch — The Emergency On/Off switch should only be used when it is required to shut the chiller off immediately. Power to the MBB, EMM, and marquee display is interrupted when this switch is off and all outputs from these modules will be turned off.
Board Addresses — The Main Base Board (MBB) has a
Control Module Communication
RED LED — Proper operation of the control boards can be visually checked by looking at the red status LEDs
GREEN LED — The MBB has one green LED. The Local Equipment Network (LEN) LED should always be blinking whenever power is on. All other boards have a LEN LED which should be blinking whenever power is on. Check LEN connections for potential communication errors at the board J3 and/or J4 connectors. Communication between modules is accomplished by a
YELLOW LED — The MBB has one yellow LED. The Sterlco Comfort Network (SCN) LED will blink during times of network communication.
Sterlco Comfort Network (SCN) Interface —
The 30RA chiller units can be connected to the SCN if desired. The communication bus wiring is a shielded,
NOTE: Conductors and drain wire must be 20 AWG (Ameri- can Wire Gage) minimum stranded, tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of
It is important when connecting to a SCN communication bus that a color coding scheme be used for the entire network to simplify the installation. It is recommended that red be used for the signal positive, black for the signal negative, and white for the signal ground. Use a similar scheme for cables contain- ing different colored wires.
3