Table 38 — Motormaster® V Program Parameters for Operating Modes

PARAMETERS

DESCRIPTION

MODE

MODE

MODE

MODE

1

2

3

4

 

 

 

 

P01

Line Voltage: 01 = low line, 02 = high line

01

02

01

02

 

P02

Sterlco Freq: 01 = 4 kHz, 02 = 6 kHz, 03 = 8 kHz

01

01

01

01

 

P03

Startup mode: flying restart

06

06

06

06

 

P04

Stop mode: coast to stop

01

01

01

01

 

P05

Standard Speed source: 01= keypad,

05

05

05

05

 

04=4-20mA (NO PI), 05= R22, 06=R134a

 

 

 

 

 

 

 

P06

TB-14 output: 01 = none

01

01

01

01

 

P08

TB-30 output: 01 = none

01

01

01

01

 

P09

TB-31 Output: 01 = none

01

01

01

01

 

P10

TB-13A function sel: 01 = none

01

01

01

01

 

P11

TB-13B function sel: 01 = none

01

01

01

01

 

P12

TB-13C function sel: 01 = none

01

01

01

01

 

P13

TB-15 output: 01 = none

01

01

01

01

 

P14

Control: 01 = Terminal strip

01

01

01

01

 

P15

Serial link: 02 = enabled 9600,8,N,2 with timer

02

02

02

02

 

P16

Units editing: 02 = whole units

02

02

02

02

 

P17

Rotation: 01 = forward only, 03 = reverse only

01

01

01

01

 

P19

Acceleration time: 10 sec

10

10

10

10

 

P20

Deceleration time: 10 sec

10

10

10

10

 

P21

DC brake time: 0

0

0

0

0

 

P22

DC BRAKE VOLTAGE 0%

0

0

0

0

 

P23

Min freq = 8 Hz ~ 100 – 160 rpm

8

8

8

8

 

P24

Max freq

60

60

50

50

 

P25

Current limit: (%)

125

110

125

110

 

P26

Motor overload: 100

100

100

100

100

 

P27

Base freq: 60 or 50 Hz

60

60

50

50

 

P28

Fixed boost: 0.5% at low frequencies

0.5

0.5

0.5

0.5

 

P29

Accel boost: 0%

0

0

0

0

 

P30

Slip compensation: 0%

0

0

0

0

 

P31

Preset spd #1: speed if loss of control signal

57

57

47

47

 

P32

Preset spd #2: 0

0

0

0

0

 

P33

Preset spd #3: 0

0

0

0

0

 

P34

Preset spd 4 default — R22 set point.

18.0

18.0

18.0

18.0

 

TB12-2 open

 

 

 

 

 

 

 

P35

Preset spd 5 default — R134a set point.

12.6

12.6

12.6

12.6

 

TB12-2 closed

 

 

 

 

 

 

 

P36

Preset spd 6 default

0

0

0

0

 

P37

Preset spd 7 default

0

0

0

0

 

P38

Skip bandwidth

0

0

0

0

 

P39

Speed scaling

0

0

0

0

 

P40

Frequency scaling 50 or 60 Hz

60

60

50

50

 

P41

Load scaling: default (not used so NA)

200

200

200

200

 

P42

Accel/decel #2: default (not used so NA)

60

60

60

60

 

P43

Serial address

1

1

1

1

 

P44

Password:111

111

111

111

111

 

P45

Speed at min signal: 8 Hz; used when PID

8

8

8

8

 

mode is disabled and 4-20mA input is at 4 mA

 

 

 

 

 

 

 

P46

Speed at max feedback: 60 or 50 Hz. Used

60

60

50

50

 

when PID disabled and 4-20mA input is at 20 mA

 

 

 

 

 

 

 

P47

Clear history? 01 = maintain. (set to 02 to clear)

01

01

01

01

 

P48

Program selection: Program 1 – 12

01

02

03

04

 

P61

PI Mode: 05= reverse, 0-5V, 01 = no PID

05

05

05

05

 

P62

Min feedback = 0 (0V *10)

0

0

0

0

 

P63

Max feedback = 50 (5V * 10)

50

50

50

50

 

P64

Proportional gain = 4%

4

4

4

4

 

P65

Integral gain = .2

.2

.2

.2

.2

 

P66

PI acell/decel (set point change filter) = 5

5

5

5

5

 

P67

Min alarm

0

0

0

0

 

P68

Max alarm

0

0

0

0

 

LEGEND

 

 

 

 

NA

Not Applicable

 

 

 

 

PID

Proportional Integral Derivative

 

 

 

 

TB

Terminal Block

 

 

 

 

72

Page 72
Image 72
Sterling 30RA010-055 manual Parameters