Table 29 — Alarm and Alert Codes (cont)
ALARM/ | ALARM |
| WHY WAS THIS | ACTION TAKEN | RESET | PROBABLE | |
ALERT | OR | DESCRIPTION | ALARM | ||||
BY CONTROL | METHOD | CAUSE | |||||
CODE | ALERT |
| GENERATED? | ||||
|
|
|
| ||||
|
|
|
|
|
|
| |
T196 | Alert | Flow Lost While Pump 1 | Cooler flow switch contacts | All compressors | Manual | Wiring error, pump | |
|
| Running | open for 3 seconds after | shut down. Pump 1 |
| circuit breaker | |
|
|
| initially made | turned off. Pump 2 will |
| tripped, contactor fail- | |
|
|
|
| be started if available. |
| ure | |
|
|
|
| Chiller allowed to run if |
|
| |
|
|
|
| Pump 2 successfully |
|
| |
|
|
|
| starts and flow switch |
|
| |
|
|
|
| is closed. |
|
| |
T197 | Alert | Flow Lost While Pump 2 | Cooler flow switch contacts | All compressors shut | Manual | Wiring error, pump | |
|
| Running | open for 3 seconds after | down. Pump 2 turned |
| circuit breaker | |
|
|
| initially made | off. Pump 1 will be |
| tripped, contactor | |
|
|
|
| started if available. |
| failure | |
|
|
|
| Chiller allowed to run if |
|
| |
|
|
|
| Pump 1 successfully |
|
| |
|
|
|
| starts and flow switch |
|
| |
|
|
|
| is closed. |
|
| |
|
|
|
|
|
|
| |
T198 | Alert | Cooler pump 1 Aux | Pump 1 Auxiliary Contacts | Chiller not allowed to | Automatic when | Wiring error, faulty | |
|
| Contacts Closed While | closed for 26 seconds | start | aux contacts open | pump contactor | |
|
| Pump Off | when pump state is off |
|
| (welded contacts) | |
T199 | Alert | Cooler pump 2 Aux | Pump 2 Auxiliary Contacts | Chiller not allowed to | Automatic when | Wiring error, faulty | |
|
| Contacts Closed While | closed for 26 seconds | start | aux contacts open | pump contactor | |
|
| Pump Off | when pump state is off |
|
| (welded contacts) | |
|
|
|
|
|
|
| |
T200 | Alert | Cooler Flow/Interlock | Cooler flow switch contacts | Chiller not allowed to | Manual | Wiring error, pump | |
|
| Contacts failed to Close | failed to close within | start. For models with |
| circuit breaker | |
|
| at | 1 minute (if cooler pump | dual pumps, the |
| tripped, contactor | |
|
|
| control is enabled) or | second pump will be |
| failure, faulty flow | |
|
|
| within 5 minutes (if cooler | started if available |
| switch or interlock | |
|
|
| pump control is not |
|
|
| |
|
|
| enabled) after |
|
|
| |
A201 | Alarm | Cooler Flow/Interlock | Flow switch opens for at | All compressors shut | Manual | Cooler pump failure, | |
|
| Contacts Opened | least 3 seconds after | down. For models with |
| faulty flow switch or | |
|
| During Normal | being initially closed | dual pumps, the |
| interlock, pump | |
|
| Operation |
| second pump will be |
| circuit breaker | |
|
|
|
| started if available |
| tripped | |
A202 | Alarm | Cooler Pump Interlock | If configured for cooler | Chiller shut down | Automatic when | Wiring error, faulty | |
|
| Closed When Pump is | pump control and flow |
| aux contacts open | pump contactor | |
|
| Off | switch input is closed for |
|
| (welded contacts) | |
|
|
| 5 minutes while pump |
|
|
| |
|
|
| output(s) are off |
|
|
| |
T203 | Alert | Loss of Communication | Master chiller MBB | Dual chiller control | Automatic | Wiring error, faulty | |
|
| with slave chiller | loses communication | disabled. Chiller runs |
| wiring, failed Slave | |
|
|
| with slave chiller MBB | as a |
| chiller MBB module, | |
|
|
|
| machine. |
| power loss at slave | |
|
|
|
|
|
| chiller, wrong slave | |
|
|
|
|
|
| address. | |
|
|
|
|
|
|
| |
T204 | Alert | Loss of Communication | Slave chiller MBB loses | Dual chiller control | Automatic | Wiring error, faulty | |
|
| with master chiller | communication with | disabled. Chiller runs |
| wiring, failed master | |
|
|
| master chiller MBB | as a |
| chiller MBB module, | |
|
|
|
| machine |
| power loss at Master | |
|
|
|
|
|
| chiller. | |
|
|
|
|
|
|
| |
T205 | Alert | Master and slave chiller | Master and slave chiller | Dual chiller routine | Automatic | SCN Address for | |
|
| with same address | have the same SCN | disabled. Master/slave |
| both chillers is the | |
|
|
| address (SCN.A) | run as |
| same. Must be | |
|
|
|
| chillers. |
| different. Check | |
|
|
|
|
|
| SCN.A under the | |
|
|
|
|
|
| OPT2 | |
|
|
|
|
|
| Configuration at both | |
|
|
|
|
|
| chillers. | |
|
|
|
|
|
|
| |
T206 | Alert | High Leaving Chilled | LWT read is greater than | Alert only. No action | Automatic | Building load greater | |
|
| Water Temperature | LCW Alert Limit, Total | taken. |
| than unit capacity, | |
|
|
| capacity is 100% and LWT |
|
| low water/brine flow | |
|
|
| is greater than LWT |
|
| or compressor fault. | |
|
|
| reading one minute ago |
|
| Check for other | |
|
|
|
|
|
| alarms/alerts. | |
A207 | Alarm | Cooler Freeze | Cooler EWT or LWT is less | Chiller shutdown | Both EWT and LWT | Faulty thermistor | |
|
| Protection | than Brine Freeze (BR.FZ) | without going through | must be at least 6 F | (T1/T2), low water | |
|
|
|
| pumpdown. Cooler | (3.3 C) above Brine | flow. | |
|
|
|
| pump continues to | Freeze point (BR.FZ). |
| |
|
|
|
| run a minimum of | Automatic for first, |
| |
|
|
|
| 5 minutes (if control | Manual reset thereaf- |
| |
|
|
|
| enabled). | ter. |
| |
|
|
|
|
|
|
| |
A208 | Alarm | EWT or LWT | Cooler EWT is less than | Chiller shutdown. | Manual | Faulty cooler pump, | |
|
| Thermistor failure | LWT by 3° F (1.7° C) for | Cooler pump shut off |
| low water flow, | |
|
|
| 1 minute after a circuit is | (if control enabled). |
| plugged fluid strainer. | |
|
|
| started |
|
|
| |
T300 | Alert | Cooler Pump 1 | Pump 1 Service | None | Automatic | Routine pump | |
|
| Scheduled | Countdown (P.1.DN) |
|
| maintenance | |
|
| Maintenance Due | expired. Complete pump 1 |
|
| required | |
|
|
| maintenance and enter |
|
|
| |
|
|
| 'YES' for Pump 1 |
|
|
| |
|
|
| Maintenance Done |
|
|
| |
|
|
| (P.1.MN) item. |
|
|
|
56