Sterling 30RA010-055 manual Energy Management Module, CEPL130351

Models: 30RA010-055

1 100
Download 100 pages 44.39 Kb
Page 18
Image 18
CEPL130351

 

CEBD430351-0396-01C

 

 

 

PWR

J1

J2

 

 

01

 

 

 

 

 

 

 

 

 

-

J4

 

J3

LEN

 

CEPL130351

 

 

STATUS

 

TEST 1

 

 

 

 

J5

 

 

 

 

 

 

 

 

 

J7

 

 

 

J6

 

TEST 2

 

 

RED LED - STATUS

GREEN LED -

ADDRESS

 

 

 

LEN (LOCAL EQUIPMENT NETWORK)

DIP SWITCH

 

Fig. 11 — Energy Management Module

Table 6 — Part Load Data Percent Displacement, Standard Units without Minimum Load Valve

30RA UNIT SIZE

CONTROL

LOADING SEQ A

LOADING SEQ B

STEPS

% Displacement

Compressor

% Displacement

Compressor

 

010,015 (60 Hz)

1

100

A1

015 (50 Hz), 018

1

50

A1

2

100

A1,A2

 

022 (60 Hz)

1

42

A1

 

2

100

A1, A2

022 (50 Hz), 025, 030

1

50

A1

2

100

A1,A2

 

032, 035 (60 Hz)

1

25

A1

40

B1

2

60

A1,A2

65

A1,B1

 

3

100

A1,A2,B1

100

A1,A2,B1

035 (50 Hz)

1

33

A1

33

B1

2

67

A1, A2

67

A1, B1

 

3

100

A1, A2, B1

100

A1, A2, B1

040

1

32

A1

37

B1

2

63

A1, A2

68

A1, B1

 

3

100

A1, A2, B1

100

A1, A2, B1

 

1

25

A1

25

B1

042, 045 (50 Hz), 050,

2

50

A1,B1

50

A1,B1

055

3

75

A1,A2,B1

75

A1,B1,B2

 

4

100

A1,A2,B1,B2

100

A1,A2,B1,B2

 

 

 

 

 

 

 

1

22

A1

22

B1

 

2

44

A1,B1

44

A1,B1

045 (60 Hz)

3

72

A1,A2,B1

72

A1,B1,B2

 

 

4

100

A1,A2,B1,B2

100

A1,A2,B1,B2

 

 

 

 

 

 

NOTE: These capacity steps may vary due to different capacity staging sequences.

18

Page 18
Image 18
Sterling 30RA010-055 manual Energy Management Module, CEPL130351