Fig. 11 — Energy Management Module
Table 6 — Part Load Data Percent Displacement, Standard Units without Minimum Load Valve
30RA UNIT SIZE | CONTROL | LOADING SEQ A | LOADING SEQ B | |||
STEPS | % Displacement | Compressor | % Displacement | Compressor | ||
| ||||||
010,015 (60 Hz) | 1 | 100 | A1 | — | — | |
015 (50 Hz), 018 | 1 | 50 | A1 | — | — | |
2 | 100 | A1,A2 | — | — | ||
| ||||||
022 (60 Hz) | 1 | 42 | A1 | — | — | |
| 2 | 100 | A1, A2 | — | — | |
022 (50 Hz), 025, 030 | 1 | 50 | A1 | — | — | |
2 | 100 | A1,A2 | — | — | ||
| ||||||
032, 035 (60 Hz) | 1 | 25 | A1 | 40 | B1 | |
2 | 60 | A1,A2 | 65 | A1,B1 | ||
| 3 | 100 | A1,A2,B1 | 100 | A1,A2,B1 | |
035 (50 Hz) | 1 | 33 | A1 | 33 | B1 | |
2 | 67 | A1, A2 | 67 | A1, B1 | ||
| 3 | 100 | A1, A2, B1 | 100 | A1, A2, B1 | |
040 | 1 | 32 | A1 | 37 | B1 | |
2 | 63 | A1, A2 | 68 | A1, B1 | ||
| 3 | 100 | A1, A2, B1 | 100 | A1, A2, B1 | |
| 1 | 25 | A1 | 25 | B1 | |
042, 045 (50 Hz), 050, | 2 | 50 | A1,B1 | 50 | A1,B1 | |
055 | 3 | 75 | A1,A2,B1 | 75 | A1,B1,B2 | |
| 4 | 100 | A1,A2,B1,B2 | 100 | A1,A2,B1,B2 | |
|
|
|
|
|
| |
| 1 | 22 | A1 | 22 | B1 | |
| 2 | 44 | A1,B1 | 44 | A1,B1 | |
045 (60 Hz) | 3 | 72 | A1,A2,B1 | 72 | A1,B1,B2 | |
| ||||||
| 4 | 100 | A1,A2,B1,B2 | 100 | A1,A2,B1,B2 | |
|
|
|
|
|
|
NOTE: These capacity steps may vary due to different capacity staging sequences.