Sterling 30RA010-055 manual B — Configuring Return Temperature Reset

Models: 30RA010-055

1 100
Download 100 pages 44.39 Kb
Page 43
Image 43
Table 26B — Configuring Return Temperature Reset

Table 26A — Configuring Outdoor Air and Space Temperature Reset

MODE

KEYPAD

SUB-

KEYPAD

 

DISPLAY

ITEM

 

ITEM

Outdoor

 

COMMENT

(RED LED)

ENTRY

MODE

ENTRY

Space

EXPANSION

 

 

 

 

 

 

 

Air

 

 

 

 

ENTER

DISP

 

 

 

 

 

 

 

 

UNIT

 

 

 

 

 

 

 

 

OPT1

 

 

 

 

 

 

 

 

OPT2

 

 

 

 

 

 

CONFIGURATION

 

 

ENTER

 

 

 

COOLING RESET

2 = Outdoor-Air Temperature

 

RSET

CRST

2

4

4 = Space Temperature

 

 

 

 

 

 

 

 

 

TYPE

(Connect to TB5-5,6)

 

 

 

 

 

 

 

 

 

 

 

 

RM.NO*

85 °F

72 °F

REMOTE - NO

Default: 125.0 F (51.7 C)

 

 

 

 

RESET TEMP

Range: 0° to125 F

 

 

 

 

 

 

 

 

 

 

 

RM.F

55 °F

68 °F

REMOTE - FULL

Default: 0.0° F (-17.7 C)

 

 

 

 

RESET TEMP

Range: 0° to 125 F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REMOTE - DEGREES

Default: 0° F (0° C)

 

 

 

 

RM.DG

15 °F

6 °F

Range: –30 to 30 F

 

 

 

 

RESET

 

 

 

 

 

 

 

(–34.4 to -1.1 °C)

 

 

 

 

 

 

 

 

*4 items skipped in this example.

Table 26B — Configuring Return Temperature Reset

MODE

KEYPAD

SUB-MODE

KEYPAD

ITEM

DISPLAY

ITEM

 

COMMENT

(RED LED)

ENTRY

 

ENTRY

 

 

EXPANSION

 

 

 

ENTER

DISP

ENTER

TEST

ON/OFF

TEST DISPLAY LEDs

 

 

 

 

UNIT

ENTER

TYPE

X

UNIT TYPE

 

 

 

 

OPT1

ENTER

FLUD

X

COOLER FLUID

 

 

 

 

OPT2

ENTER

CTRL

X

CONTROL METHOD

 

 

 

 

 

ENTER

 

 

 

0

= No Reset

 

 

 

 

 

 

1

= 4 to 20 mA Input (EMM required)

 

 

 

 

 

 

 

CONFIGURATION

 

RSET

 

CRST

X

COOLING RESET TYPE

2

(Connect to EMM TB6-2,3)

 

 

 

= Outdoor-Air Temperature

 

 

 

 

 

 

 

3

= Return Fluid

 

 

 

 

 

 

 

4

= Space Temperature

 

 

 

 

 

 

 

 

(Connect to TB5-5,6)

 

 

 

 

RT.NO*

XXX.X F

RETURN FLUID - NO

Default: 10.0 F (5.6 C)

 

 

 

 

RESET TEMP

Range: 0° to125 F COOLER T

 

 

 

 

 

 

 

 

 

 

RT.F

XXX.X F

RETURN FLUID - FULL

Default: 0 F (–17.8 C)

 

 

 

 

RESET TEMP

Range: 0° to 125 F COOLER T

 

 

 

 

 

 

 

 

 

 

RT.DG

XX.X F

RETURN - DEGREES

Default: 0 F (0 C)

 

 

 

 

RESET

Range: –30 to 30°F (–16.7 to 16.7 C)

 

 

 

 

 

 

*4 items skipped in this example.

Temperature Reset — The control system is capable of handling leaving-fluid temperature reset based on return cooler fluid temperature. Because the change in temperature through the cooler is a measure of the building load, the return tempera- ture reset is in effect an average building load reset method. The control system is also capable of temperature reset based on outdoor-air temperature (OAT), space temperature (SPT), or from an externally powered 4 to 20 mA signal. Accessory sen- sors must be used for SPT reset (33ZCT55SPT). The Energy Management Module (EMM) must be used for temperature reset using a 4 to 20 mA signal. See Tables 25A and 25B.

IMPORTANT: Care should be taken when interfacing with other control systems due to possible power supply differ- ences: full wave bridge versus half wave rectification. Con- nection of control devices with different power supplies may result in permanent damage. ComfortLink™ controls incorporate power supplies with half wave rectification. A signal isolation device should be utilized if the signal gen- erator incorporates a full wave bridge rectifier.

To use Outdoor Air or Space Temperature reset, four vari- ables must be configured. In the Configuration mode under the sub-mode RSET, items CRST, RM.NO, RM.F and RT.DG must be properly set. See Table 26A — Configuring Outdoor Air and Space Temperature Reset. The outdoor air reset exam- ple provides 0° F (0° C) chilled water set point reset at 85.0 F (29.4 C) outdoor-air temperature and 15.0 F (8.3 C) reset at

55.0F (12.8 C) outdoor-air temperature. The space tempera- ture reset example provides 0° F (0° C) chilled water set point reset at 72.0 F (22.2 C) space temperature and 6.0 F (3.3 C) reset at 68.0 F (20.0 C) space temperature. The variable CRST should be configured for the type of reset desired. The variable RM.NO should be set to the temperature that no reset should occur. The variable RM.F should be set to the temperature that maximum reset is to occur. The variable RM.DG should be set to the maximum amount of reset desired.

To use Return reset, four variables must be configured. In the Configuration mode under the sub-mode RSET, items CRST, RT.NO, RT.F and RT.DG must be properly set. See Table 26B — Configuring Return Temperature Reset. This ex- ample provides 5.0 F (2.8 C) chilled water set point reset at

43

Page 43
Image 43
Sterling 30RA010-055 manual B — Configuring Return Temperature Reset