Table 16 — Outputs Mode and Sub-Mode Directory
KEYPAD | ITEM | DISPLAY | ITEM | COMMENT | ||||
ENTRY | EXPANSION | |||||||
|
|
|
| |||||
GEN.O |
|
|
|
|
| GENERAL OUTPUTS |
| |
|
|
|
| FAN1 | ON/OFF | FAN 1 RELAY |
| |
|
| ENTER |
|
| ||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
| FAN2 | ON/OFF | FAN 2 RELAY |
| |
|
|
|
|
|
|
|
| |
|
|
|
| C.WP1 | ON/OFF | COOLER PUMP RELAY 1 |
| |
|
|
|
|
|
|
|
| |
|
|
|
| C.WP2 | ON/OFF | COOLER PUMP RELAY 2 |
| |
|
|
|
|
|
|
|
| |
|
|
|
| CLHT | ON/OFF | COOLER/PUMP HEATER |
| |
|
|
|
|
|
|
|
| |
|
|
|
| MLV.R | ON/OFF | MINIMUM LOAD VALVE RELAY |
| |
|
|
|
|
|
|
|
| |
CIR.A |
|
|
|
|
| OUTPUTS CIRCUIT A |
| |
|
|
| CC.A1 | ON/OFF | COMPRESSOR A1 RELAY |
| ||
|
| ENTER |
|
| ||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
| CC.A2 | ON/OFF | COMPRESSOR A2 RELAY |
| |
|
|
|
|
|
|
|
| |
CIR.B |
|
|
|
|
| OUTPUTS CIRCUIT B | See Note | |
|
|
| CC.B1 | ON/OFF | COMPRESSOR B1 RELAY |
| ||
|
| ENTER |
|
| ||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
| CC.B2 | ON/OFF | COMPRESSOR B2 RELAY |
| |
|
|
|
|
|
|
|
|
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
Table 17 — Configuration Mode and
KEYPAD | ITEM | DISPLAY | ITEM |
|
| COMMENT |
| ||||
ENTRY | EXPANSION |
|
|
| |||||||
|
|
|
|
|
|
|
| ||||
DISP |
|
|
|
|
| DISPLAY CONFIGURATION |
|
|
|
|
|
|
|
|
| TEST | ON/OFF | TEST DISPLAY LEDS |
|
|
|
|
|
|
| ENTER |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| METR | ON/OFF | METRIC DISPLAY | Off = English; On = Metric | ||||
|
|
|
|
|
|
|
|
|
| ||
|
|
|
| LANG | X | LANGUAGE SELECTION |
| Default: 0 |
| ||
|
|
|
|
|
|
|
| 0 = English |
| ||
|
|
|
|
|
|
|
| 1 = Espanol |
| ||
|
|
|
|
|
|
|
| 2 = Francais |
| ||
|
|
|
|
|
|
|
| 3 = Portuguese |
| ||
|
|
|
| PAS.E | ENBL/DSBL | PASSWORD ENABLE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| PASS | xxxx | SERVICE PASSWORD |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
UNIT |
|
|
|
| UNIT CONFIGURATION |
|
|
|
|
| |
| ENTER |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| SZA.1 | XX | COMPRESSOR A1 SIZE | Unit Size |
| 60 Hz |
| 50 Hz |
|
|
|
|
|
|
| 010 |
| 10 |
| 11 |
|
|
|
|
|
|
| 015 |
| 15 |
| 7 |
|
|
|
|
|
|
| 018 |
| 9 |
| 9 |
|
|
|
|
|
|
| 022 |
| 9 |
| 11 |
|
|
|
|
|
|
| 025 |
| 13 |
| 13 |
|
|
|
|
|
|
| 030 |
| 15 |
| — |
|
|
|
|
|
|
| 032 |
| — |
| 8 |
|
|
|
|
|
|
| 035 |
| 9 |
| 13 |
|
|
|
|
|
|
| 040 |
| 13 |
| — |
|
|
|
|
|
|
| 042 |
| — |
| 11 |
|
|
|
|
|
|
| 045 |
| 10 |
| 13 |
|
|
|
|
|
|
| 050 |
| 13 |
| — |
|
|
|
|
|
|
| 055 |
| 15 |
| — |
|
|
|
| SZA.2 | XX | COMPRESSOR A2 SIZE | Unit Size |
| 60 Hz |
| 50 Hz |
|
|
|
|
|
|
| 015 |
| — |
| 7 |
|
|
|
|
|
|
| 018 |
| 9 |
| 9 |
|
|
|
|
|
|
| 022 |
| 13 |
| 11 |
|
|
|
|
|
|
| 025 |
| 13 |
| 13 |
|
|
|
|
|
|
| 030 |
| 15 |
| — |
|
|
|
|
|
|
| 032 |
| — |
| 11 |
|
|
|
|
|
|
| 035 |
| 13 |
| 13 |
|
|
|
|
|
|
| 040 |
| 13 |
| — |
|
|
|
|
|
|
| 042 |
| — |
| 11 |
|
|
|
|
|
|
| 045 |
| 13 |
| 13 |
|
|
|
|
|
|
| 050 |
| 13 |
| — |
|
|
|
|
|
|
| 055 |
| 15 |
| — |
|
|
|
| SZB.1 | XX | COMPRESSOR B1 SIZE | Unit Size |
| 60 Hz |
| 50 Hz |
|
|
|
|
|
|
| 032 |
| — |
| 13 |
|
|
|
|
|
|
| 035 |
| 15 |
| 13 |
|
|
|
|
|
|
| 040 |
| 15 |
| — |
|
|
|
|
|
|
| 042 |
| — |
| 11 |
|
|
|
|
|
|
| 045 |
| 10 |
| 13 |
|
|
|
|
|
|
| 050 |
| 13 |
| — |
|
|
|
|
|
|
| 055 |
| 15 |
| — |
|
|
|
| SZB.2 | XX | COMPRESSOR B2 SIZE | Unit Size |
| 60 Hz |
| 50 Hz |
|
|
|
|
|
|
| 042 |
| — |
| 11 |
|
|
|
|
|
|
| 045 |
| 13 |
| 13 |
|
|
|
|
|
|
| 050 |
| 13 |
| — |
|
|
|
|
|
|
| 055 |
| 15 |
| — |
|
|
|
| SH.SP | XX.X ∆F | SUPERHEAT SETPOINT |
|
| Default: 15 °F |
| |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| REFG | X | REFRIGERANT |
|
| 1 = |
| |
|
|
|
|
|
|
|
|
| |||
|
|
|
| FAN.S |
| FAN STAGING SELECT | 1 = One Fan |
| |||
|
|
|
|
|
|
| 2 = Two Fans |
| |||
|
|
|
|
|
|
| 3 = Three Fans |
| |||
|
|
|
|
|
|
| 4 = Four Fans |
|
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
31