SPT (T10) PART NO. 33ZCT55SPT | |
| SENSOR |
SEN | TB5 |
SEN | |
| 5 |
| 6 |
Fig. 9 — Typical Space Temperature
Sensor Wiring
|
| |
|
| SENSOR |
|
| 6 |
| SCN+ | 5 |
TO SCN | SCN GND | 4 |
COMM 1 |
|
|
BUS (PLUG) |
| 3 |
AT UNIT |
|
|
| SCN- | 2 |
|
| 1 |
Fig. 10 — SCN Communications Bus Wiring to Optional Space Sensor RJ11 Connector
Energy Management Module (Fig. 11) — This
•4 to 20 mA leaving fluid temperature reset (requires
•4 to 20 mA cooling set point reset (requires field- supplied 4 to 20 mA generator)
•Discrete inputs for
•4 to 20 mA demand limit (requires
•Discrete input for Ice Done switch (requires field- supplied dry contacts capable of handling a 24 vac, 50 mA load)
See Demand Limit and Temperature Reset sections on pages 44 and 43 for further details.
Care should be taken when interfacing with other manufac- turer’s control systems due to possible power supply differences, full wave bridge versus half wave rectification. The two different power supplies cannot be mixed. ComfortLink™ controls use half wave rectification. A signal isolation device should be utilized if a full wave bridge signal generating device is used.
Thermostatic Expansion Valves (TXV) — All units are equipped from the factory with conventional TXVs. Each
refrigeration circuit is also supplied with a
The TXV is set at the factory to maintain approximately 8 to 12° F (4.4 to 6.7° C) suction superheat leaving the cooler by metering the proper amount of refrigerant into the cooler. All TXVs are adjustable, but should not be adjusted unless absolutely necessary.
The TXV is designed to limit the cooler saturated suction temperature to 55 F (12.8 C). This makes it possible for unit to start at high cooler fluid temperatures without overloading the compressor.
Capacity Control — The control system cycles com- pressors, and minimum load valve solenoids (if equipped) to maintain the
The control has an automatic
The TXVs will provide a controlled
If a circuit is to be stopped, the compressor with the lowest wear factor will be shut off first in most cases. Certain override conditions may shut off the smaller of two compressors on a circuit first.
The capacity control algorithm runs every 30 seconds. The algorithm attempts to maintain the Control Point at the desired set point. Each time it runs, the control reads the entering and leaving fluid temperatures. The control determines the rate at which conditions are changing and calculates 2 variables based on these conditions. Next, a capacity ratio is calculated using the 2 variables to determine whether or not to make any changes to the current stages of capacity. This ratio value ranges from
17