Table 29 — Alarm and Alert Codes (cont)

ALARM/

ALARM

 

WHY WAS THIS

ACTION TAKEN

RESET

PROBABLE

ALERT

OR

DESCRIPTION

ALARM

BY CONTROL

METHOD

CAUSE

CODE

ALERT

 

GENERATED?

 

 

 

 

 

 

 

 

 

 

 

A140

Alert

Reverse Rotation

Incoming chiller power

Chiller not allowed to

Manual

Reverse any two

 

 

Detected

leads not phased correctly

start.

 

incoming power

 

 

 

 

 

 

leads to correct.

 

 

 

 

 

 

Check for correct fan

 

 

 

 

 

 

rotation first.

 

 

 

 

 

 

 

A150

Alarm

Emergency Stop

SCN emergency stop

Chiller shutdown

Automatic once SCN

SCN Network

 

 

 

command received

without going through

command for

command.

 

 

 

 

pumpdown.

EMSTOP returns to

 

 

 

 

 

 

normal

 

 

 

 

 

 

 

 

A151

Alarm

Illegal Configuration

One or more illegal

Chiller is not allowed to

Manual once

Configuration error.

 

 

 

configurations exists.

start.

configuration errors

Check unit settings.

 

 

 

 

 

are corrected

 

 

 

 

 

 

 

 

A152

Alarm

Unit Down Due to

Both circuits are down due

Chiller is unable

Automatic once

Alarm notifies user

 

 

Failure

to alarms/alerts.

to run.

alarms/alerts are

that chiller is 100%

 

 

 

 

 

cleared that prevent

down.

 

 

 

 

 

the chiller from

 

 

 

 

 

 

starting.

 

 

 

 

 

 

 

 

T153

Alert

Real Time Clock

Internal clock on MBB fails

Occupancy schedule

Automatic when

Time/Date/Month/

 

 

Hardware Failure

 

will not be used. Chiller

correct clock control

Day/Year not

 

 

 

 

defaults to Local On

restarts.

properly set.

 

 

 

 

mode.

 

 

 

 

 

 

 

 

 

A154

Alarm

Serial EEPROM

Hardware failure with MBB

Chiller is unable

Manual

Main Base Board

 

 

Hardware Failure

 

to run.

 

failure.

 

 

 

 

 

 

 

T155

Alert

Serial EEPROM

Configuration/storage

No Action

Manual

Potential failure of

 

 

Storage Failure

failure with MBB

 

 

MBB. Download

 

 

 

 

 

 

current operating

 

 

 

 

 

 

software. Replace

 

 

 

 

 

 

MBB if error occurs

 

 

 

 

 

 

again.

A156

Alarm

Critical Serial EEPROM

Configuration/storage

Chiller is not allowed

Manual

Main Base Board

 

 

Storage Failure

failure with MBB

to run.

 

failure.

A157

Alarm

A/D Hardware Failure

Hardware failure with

Chiller is not allowed

Manual

Main Base Board

 

 

 

peripheral device

to run.

 

failure.

A189

Alarm

Cooler pump auxiliary

Pump 1 (2) aux contacts

Both pump outputs

Manual

Wiring error, faulty

 

 

contact inputs miswired

closed when pump 2 (1)

are turned off.

 

pump contactor

 

 

 

energized.

 

 

auxiliary contacts.

T173

Alert

Loss of Communication

MBB loses communication

4 to 20 mA

Automatic

Wiring error, faulty

 

 

with EMM

with EMM

temperature reset

 

wiring or failed

 

 

 

 

disabled. Demand

 

Energy Manage-

 

 

 

 

Limit set to 100%. 4 to

 

ment Module (EMM).

 

 

 

 

20 mA set point

 

 

 

 

 

 

disabled.

 

 

 

 

 

 

 

 

 

T174

Alert

4 to 20 mA Cooling Set

If configured with EMM and

Set point function

Automatic

Faulty signal

 

 

Point Input Failure

input less than 2 mA or

disabled. Chiller

 

generator, wiring

 

 

 

greater than 22 mA

controls to CSP1.

 

error, or faulty EMM.

T176

Alert

4 to 20 mA

If configured with EMM

Reset function

Automatic

Faulty signal

 

 

Temperature Reset

and input less than 2 mA or

disabled. Chiller

 

generator, wiring

 

 

Input Failure

greater than 22 mA

returns to normal set

 

error, or faulty EMM.

 

 

 

 

point control.

 

 

 

 

 

 

 

 

 

T177

Alert

4 to 20 mA Demand

If configured with EMM and

Demand limit function

Automatic

Faulty signal

 

 

Limit Input Failure

input less than 2 mA or

disabled. Chiller

 

generator, wiring

 

 

 

greater than 22 mA

returns to 100%

 

error, or faulty EMM.

 

 

 

 

demand limit

 

 

 

 

 

 

control.

 

 

 

 

 

 

 

 

 

T189

Alarm

Cooler pump 2 and

Alarm is generated when

Chiller not allowed to

Manual

Wiring error

 

 

Aux Contact Input

the pump’s aux contacts

start

 

 

 

 

miswired

close when a pump is

 

 

 

 

 

 

called for

 

 

 

T190

Alert

Cooler pump 1 Aux

Pump 1 Auxiliary Contacts

Pump 1 turned off.

Manual

Wiring error, faulty

 

 

Contacts Failed to Close

did not close within

Pump 2 will be started

 

contacts on pump

 

 

at Start-Up

26 seconds after pump

if available.

 

contactor

 

 

 

was started

 

 

 

T191

Alert

Cooler pump 2 Aux

Pump 2 Auxiliary Contacts

Pump 2 turned off.

Manual

Wiring error, faulty

 

 

Contacts Failed to Close

did not close within

Pump 1 will be started

 

contacts on pump

 

 

at Start-Up

26 seconds after pump

if available.

 

contactor

 

 

 

was started

 

 

 

 

 

 

 

 

 

 

T192

Alert

Cooler pump 1 Failed

Pump 1 did not provide

Pump 1 turned off.

Manual

Wiring error, pump

 

 

to Provide Flow at

flow to close flow switch

Pump 2 will be started

 

circuit breaker

 

 

Start-Up

within 60 seconds

if available.

 

tripped, contactor

 

 

 

 

 

 

failure

T193

Alert

Cooler pump 2 Failed

Pump 2 did not provide

Pump 1 turned off.

Manual

Wiring error, pump

 

 

to Provide Flow at

flow to close flow switch

Pump 2 will be started

 

circuit breaker

 

 

Start-Up

within 60 seconds

if available.

 

tripped, contactor

 

 

 

 

 

 

failure

T194

Alert

Cooler pump 1 Aux

Pump 1 Auxiliary Contacts

Pump 2 will be started

Manual

Wiring error, faulty

 

 

Contacts Opened

open for 26 seconds after

if available. Chiller

 

contacts on pump

 

 

During Normal

initially made. All

allowed to run if

 

contactor

 

 

Operation

compressors shut down.

Pump 2 successfully

 

 

 

 

 

Pump 1 turned off.

starts.

 

 

T195

Alert

Cooler pump 2 Aux

Pump 2 Auxiliary Contacts

Pump 1 will be started

Manual

Wiring error, faulty

 

 

Contacts Opened

open for 26 seconds after

if available. Chiller

 

contacts on pump

 

 

During Normal

initially made. All

allowed to run if

 

contactor

 

 

Operation

compressors shut down.

Pump 1 successfully

 

 

 

 

 

Pump 2 turned off.

starts.

 

 

55

Page 55
Image 55
Sterling 30RA010-055 manual Alarm and Alert Codes cont